Date Code 20060320
Instruction Manual
SEL-311C Relay
Appendix F
Setting Negative-Sequence
Overcurrent Elements
Setting Negative-Sequence
Definite-Time Overcurrent Elements
Negative-sequence instantaneous overcurrent elements 50Q1 through
50Q4 and 67Q1 through 67Q4 should not be set to trip directly.
This is
because negative-sequence current can transiently appear when a circuit
breaker is closed and balanced load current suddenly appears.
To avoid tripping for this transient condition, use negative-sequence definite-
time overcurrent elements 67Q1T through 67Q4T with at least 1.5 cycles of
time delay (transient condition lasts less than 1.5 cycles). For example, make
time delay setting:
67Q1D =
1.50
for negative-sequence definite-time overcurrent element 67Q1T. Refer to
for more information on negative-sequence instantaneous and
definite-time overcurrent elements.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...