10.36
SEL-311C Relay
Instruction Manual
Date Code 20060320
Serial Port Communications and Commands
Command Explanations
OPE Command (Open Breaker)
The
OPE
command asserts Relay Word bit OC for 1/4 cycle when it is
executed. Relay Word bit OC can then be programmed into the SEL
OGIC
control equation TR to assert the TRIP Relay Word bit, which in turn asserts
an output contact (e.g., OUT101 = TRIP) to trip a circuit breaker. See
.
for more information concerning
Relay Word bit OC and its recommended use, as used in the factory settings.
To issue the
OPE
command, enter the following:
==>
OPE <Enter>
Open Breaker (Y/N) ?
Y <Enter>
Are you sure (Y/N) ?
Y <Enter>
==>
Typing
N <Enter>
after either of the above prompts will abort the command.
The
OPE
command is supervised by the main board Breaker jumper (see
). If the Breaker jumper is not in place (Breaker jumper = OFF), the
relay does not execute the
OPE
command and responds:
Aborted: No Breaker Jumper
PUL Command (Pulse Output Contact)
The
PUL
command allows you to pulse any of the output contacts for a
specified length of time. The command format is:
PUL
x y
To pulse
OUT101
for 5 seconds:
==>
PUL OUT101 5 <Enter>
Are you sure (Y/N) ?
Y <Enter>
==>
If the response to the
Are you sure (Y/N) ?
prompt is
N
or
n
, the command
is aborted.
The
PUL
command is supervised by the main board Breaker jumper (see
). If the Breaker jumper is not in place (Breaker jumper = OFF), the
relay does not execute the
PUL
command and responds:
Aborted: No Breaker Jumper
The relay generates an event report if any of the
OUT101
through
OUT107
contacts are pulsed. The
PUL
command is primarily used for testing purposes.
where:
x
= the output name (e.g.
OUT101
,
OUT107
,
ALARM
,
OUT211
—see
and
).
y
= the pulse duration (1–30 seconds). If
y
is not specified, the
pulse duration defaults to 1 second.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...