7.19
Date Code 20060320
Instruction Manual
SEL-311C Relay
Inputs, Outputs, Timers, and Other Control Logic
Multiple Setting Groups
Multiple Setting Groups
The relay has six (6) independent setting groups. Each setting group has
complete relay (distance, overcurrent, reclosing, etc.) and SEL
OGIC
control
equation settings.
Active Setting
Group Indication
Only one setting group can be active at a time. Relay Word bits SG1–SG6
indicate the active setting group:
For example, if setting Group 4 is the active setting group, Relay Word bit
SG4 asserts to logical 1, and the other Relay Word bits, SG1, SG2, SG3, SG5,
and SG6, are all deasserted to logical 0.
Selecting the Active
Setting Group
The active setting group is selected with
one
of the following:
➤
SEL
OGIC
control equation settings SS1–SS6.
➤
The serial port
GROUP
command (see
).
➤
The front-panel
{GROUP}
pushbutton (see
Panel Interface (Only on Models With LCD)
SEL
OGIC
control equation settings SS1–SS6 have priority over the serial port
GROUP
command and the front-panel
{GROUP}
pushbutton in selecting the
active setting group.
Operation of SEL
OGIC
Control Equation
Settings SS1–SS6
Each setting group has its own set of SEL
OGIC
control equation settings SS1–
SS6.
The operation of these settings is explained with an example.
Table 7.4
Definitions for Active Setting Group
Indication Relay Word Bits SG1–SG6
Relay Word Bit
Definition
SG1
Indication that setting Group 1 is the active setting group
SG2
Indication that setting Group 2 is the active setting group
SG3
Indication that setting Group 3 is the active setting group
SG4
Indication that setting Group 4 is the active setting group
SG5
Indication that setting Group 5 is the active setting group
SG6
Indication that setting Group 6 is the active setting group
Table 7.5
Definitions for Active Setting Group Switching SEL
OGIC
Control
Equation Settings SS1–SS6
Setting
Definition
SS1
go to (or remain in) setting Group 1
SS2
go to (or remain in) setting Group 2
SS3
go to (or remain in) setting Group 3
SS4
go to (or remain in) setting Group 4
SS5
go to (or remain in) setting Group 5
SS6
go to (or remain in) setting Group 6
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...