Inputs, Outputs, Timers, and Other Control Logic
Latch Control Switches
Latch Control Switches
The latch control switches are enabled using the ELAT setting. Set ELAT to
the number of latch control switches that are desired (N, 1–16).
The latch control switch feature of this relay replaces latching relays.
Traditional latching relays maintain their output contact state when set. The
SEL-311C latch bit retains memory even when control power is lost. If the
latch bit is set to a programmable output contact and control power is lost, the
state of the latch bit is stored in nonvolatile memory but the output contact will
go to its de-energized state. When the control power is applied back to the
relay, the programmed output contact will go back to the state of the latch bit.
The state of a traditional latching relay output contact is changed by pulsing
the latching relay inputs (see
). Pulse the set input to close (“set”)
the latching relay output contact. Pulse the reset input to open (“reset”) the
latching relay output contact. Often the external contacts wired to the latching
relay inputs are from remote control equipment (e.g., SCADA, RTU).
Figure 7.11
Traditional Latching Relay
The sixteen (16) latch control switches in the SEL-311C provide latching
relay type functions.
Figure 7.12
Latch Control Switches Drive Latch Bits LT1 Through LT16
The output of the latch control switch in
is a Relay Word bit LT
n
(
n
= 1–16), called a latch bit. The latch control switch logic in
repeats for each latch bit LT1–LT16. Use these latch bits in SEL
OGIC
control
equations.
These latch control switches each have the following SEL
OGIC
control
equation settings:
SETn
(set latch bit LT
n
to logical 1)
RSTn
(reset latch bit LT
n
to logical 0)
If setting SET
n
asserts to logical 1, latch bit LT
n
asserts to logical 1. If setting
RST
n
asserts to logical 1, latch bit LT
n
deasserts to logical 0. If both settings
SET
n
and RST
n
assert to logical 1, setting RST
n
has priority and latch bit LT
n
deasserts to logical 0.
Output
Contact
Traditional Latching Relay
Reset
Input
Set
Input
(—)
(+)
LTn
SETn
RSTn
(Set)
(Reset)
(n = 1 through 16)
Relay
Word
Bit
SEL
OGIC
Setting
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...