8.15
Date Code 20060320
Instruction Manual
SEL-311C Relay
Breaker Monitor and Metering Functions
Station DC Battery Monitor
Station DC Battery Monitor
The station dc battery monitor in the SEL-311C can alarm for under- or
overvoltage dc battery conditions and give a view of how much the station dc
battery voltage dips when tripping, closing, and other dc control functions
take place. The monitor measures the station dc battery voltage applied to the
rear-panel terminals labeled
Z25
and
Z26
(see
). The station dc
battery monitor settings (DCLOP and DCHIP) are available via the
SET G
command (see
and also
Global Settings (Serial Port Command SET
G and Front Panel) on page SET.22
DC Under- and
Overvoltage
Elements
. The station dc battery monitor compares the measured
station battery voltage (Vdc) to the undervoltage (low) and overvoltage (high)
pickups DCLOP and DCHIP. The setting range for pickup settings DCLOP
and DCHIP is:
OFF, 20 to 300 Vdc, .01 Vdc increments
This range allows the SEL-311C to monitor nominal battery voltages of 24,
48, 110, 125, and 250 V. When testing the pickup settings DCLOP and
DCHIP,
do not
operate the SEL-311C outside of the power supply limits
listed in
Figure 8.9
DC Under- and Overvoltage Elements
Logic outputs DCLO and DCHI in
Create Desired Logic
for DC Under- and
Overvoltage Alarming
Pickup settings DCLOP and DCHIP are set independently. Thus, they can be
set:
DCLOP < DCHIP or DCLOP > DCHIP
shows the resultant dc voltage elements that can be created with
SEL
OGIC
control equations for these two setting cases. In these two examples,
the resultant dc voltage elements are time-qualified by timer SV4T and then
routed to output contact
OUT106
for alarm purposes.
DCLO = 1 (logical 1), if V
dc
≤
pickup setting DCLOP
= 0 (logical 0), if V
dc
> pickup setting DCLOP
DCHI = 1 (logical 1), if V
dc
≥
pickup setting DCHIP
= 0 (logical 0), if V
dc
< pickup setting DCHIP
DCLO
DCHI
Vdc
Relay
Word
Bits
DCLOP
DCHIP
Settings
Undervoltage
Overvoltage
(From Rear
Panel Terminals
Labeled POWER)
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...