4.22
SEL-311C Relay
Instruction Manual
Date Code 20060320
Loss-of-Potential, CCVT Transient Detection, Load-Encroachment, and Directional Element Logic
Directional Control Settings
Most communications-assisted trip schemes set with Zone 3/ Level 3 element
direction reverse (DIR3 = R).
ORDER—Ground Directional Element Priority Setting
Setting Range:
Q (Negative-sequence voltage-polarized directional element)
V (Zero-sequence voltage-polarized directional element)
I (Channel IP current-polarized directional element)
Setting ORDER can be set with any combination of Q, V, and I. The
order
in
which these directional elements are listed determines the priority in which
they operate to provide Best Choice Ground Directional logic control. See
.
For example, if setting:
ORDER =
QV
then the first listed directional element (Q = negative-sequence voltage-
polarized directional element; see
) is the first priority directional
element to provide directional control for the ground distance and residual
ground overcurrent elements.
If the negative-sequence voltage-polarized directional element is not operable
(i.e., it does not have sufficient operating quantity as indicated by its internal
enable, 32QGE, not being asserted), then the second listed directional element
(V = zero-sequence voltage-polarized directional element; see
)
provides directional control for the ground distance and residual ground
overcurrent elements.
Another example, if setting:
ORDER =
V
then the zero-sequence voltage-polarized directional element (V = zero-
sequence voltage-polarized directional element; see
) provides
directional control for the ground distance and residual ground overcurrent
elements all the time.
Setting ORDER can be set with any element combination (e.g.,
ORDER = IQV, ORDER = QVI, ORDER = IV, ORDER = VQ, ORDER = I,
ORDER = Q).
If ground quadrilateral distance elements are used, the first entry in the
ORDER setting should be as shown in
.
DIR3 = F or R
M3P (
M3PT (
)
Z3G (
Z3GT (
67G3 (
67G3T (
67Q3 (
)
67Q3T (
DIR4 = F or R
M4P (
M4PT (
)
Z4G (
Z4GT (
67G4 (
67G4T (
67Q4 (
)
67Q4T (
Table 4.2
Elements Controlled by Zone/Level Direction Settings (Corresponding Overcurrent and Directional
Element Figure Numbers in Parentheses)
(Sheet 2 of 2)
Level
Direction
Settings
Phase Distance
Ground Distance
Residual Ground
Negative-Sequence
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...