5.32
SEL-311C Relay
Instruction Manual
Date Code 20060320
Trip and Target Logic
Front-Panel Target LEDs
TIME Target LED
The
TIME
target LED illuminates at the rising edge of trip if SEL
OGIC
control
equation setting FAULT has been asserted for more than three cycles. FAULT
is usually set with distance and time-overcurrent element pickups (e.g.,
FAULT = 51G + 51Q + M2P + Z2G) to detect fault inception. If tripping
occurs more than three cycles after fault inception, the
TIME
target illuminates.
SEL
OGIC
control equation setting FAULT also controls maximum/minimum
metering. If FAULT is asserted, maximum/minimum metering is blocked (see
Maximum/Minimum Metering on page 8.29
). Fault current values are not to be
accrued as maximum current values in maximum/minimum metering.
COMM Target LED
The
COMM
target LED illuminates at the rising edge of trip if the trip is the sole
and direct result of SEL
OGIC
control equation setting TRCOMM and
associated communications-assisted trip logic, Relay Word bit ECTT, or
SEL
OGIC
control equation setting DTT (see
, top half of figure).
Another Application for the COMM Target LED
If none of the traditional communications-assisted trip logic is used (i.e.,
SEL
OGIC
control equation setting TRCOMM is not used), consideration can
be given to using the
COMM
target LED to
indicate tripping via remote
communications channels
(e.g., via serial port commands or SCADA
asserting optoisolated inputs). Use SEL
OGIC
control equation setting DTT
(Direct Transfer Trip) to accomplish this (see
).
For example, if the
OPEN
command or remote bit RB1 [see
(Control Remote Bit) on page 10.37
] are used to trip via the serial port and
they should illuminate the
COMM
target LED, set them in SEL
OGIC
control
equation setting DTT:
DTT =
… + OC + RB1
Additionally, if SCADA asserts optoisolated input
IN104
to trip and it should
illuminate the
COMM
target LED, set it in SEL
OGIC
control equation setting
DTT also:
DTT =
… + IN104 + …
Relay Word bits set in SEL
OGIC
control equation setting DTT do not have to
be set in SEL
OGIC
control equation setting TR–both settings directly assert the
TRIP Relay Word bit. The only difference between settings DTT and TR is
that setting DTT causes the
COMM
target LED to illuminate.
Many other variations of the above DTT settings examples are possible.
SOTF Target LED
The
SOTF
target LED illuminates at the rising edge of the TRIP Relay Word bit
if the trip is the sole and direct result of the SEL
OGIC
control equation setting
TRSOTF and associated switch-onto-fault trip logic (see
79 Target LEDs
If the reclosing relay is turned off (enable setting E79 = N or 79OI1 = 0), all
the Device 79 (reclosing relay) target LEDs are extinguished.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...