10.17
Date Code 20060320
Instruction Manual
SEL-311C Relay
Serial Port Communications and Commands
Command Explanations
=>
COM L <Enter>
SEL-311C POTT Date: 10/12/99 Time: 16:24:01.623
EXAMPLE: BUS B, BREAKER 3
FID=SEL-311C-R100-V0-Z001001-D19991118 CID=FF27
Summary for Mirrored Bits channel A
For 10/05/99 17:18:12.993 to 10/10/99 18:37:36.123
Total failures 4 Last error Relay Disabled
Relay Disabled 2
Data error 0 Longest Failure 2.835 sec.
Re-Sync 0
Underrun 1 Unavailability 0.000003
Overrun 0
Parity error 1
Framing error 0 Loopback 0
Bad Re-Sync 0
Failure Recovery
# Date Time Date Time Duration Cause
1 10/05/99 18:36:09.279 10/05/9918:37:36.114 2.835 Relay Disabled
2 10/06/99 13:18:09.236 10/06/99 13:18:09.736 0.499 Parity error
3 10/07/99 11:43:35.547 10/07/99 11:43:35.637 0.089 Underrun
4 10/09/99 17:18:12.993 10/09/99 17:18:13.115 0.121 Relay Disabled
=>
There may be up to 255 records in the extended report. To limit the number of
COMM records displayed in the report to the 10 most recent records, type
COM 10 L <Enter>
. To select lines 10 through 20 of the COMM records for
display in the report, type
COM 10 20 L <Enter>
. To reverse the order of the
COMM records in the report, supply a range of row numbers, with the larger
number first, i.e.,
COM 40 10 L <Enter>
. To display all the COMM records
that started on a particular day, supply that date as a parameter, i.e.,
COM 2/8/
98 L <Enter>
. To display all the COMM records that started between a range
of dates, supply both dates as parameters, i.e.,
COM 2/21/98 2/7/98 L
<Enter>
. Reversing the order of the dates will reverse the order of the records
in the report. To receive a summary report for a subset of the records, use one
of the above methods while omitting the L parameter.
To clear the COMM records, type
COM C <Enter>
. The prompting message
Are you sure (Y/N) ?
is displayed. Typing
N <Enter>
aborts the clearing
operation with the message
Canceled
. If both M
IRRORED
B
ITS
channels are
enabled, omitting the channel specifier in the clear command will cause both
channels to be cleared.
DAT Command (View/Change Date)
DAT
displays the date stored by the internal calendar/clock. If the date format
setting DATE_F is set to MDY, the date is displayed as month/day/year. If the
date format setting DATE_F is set to YMD, the date is displayed as year/
month/day.
To set the date, type
DAT mm/dd/yy <Enter>
if the DATE_F setting is MDY.
If the DATE_F is set to YMD, enter
DAT yy/mm/dd <Enter>
. To set the date
to June 1, 1999, enter when DATE_F = MDY:
=>
DAT 6/1/99 <Enter>
06/01/99
=>
You can separate the month, day, and year parameters with spaces, commas,
slashes, colons, and semicolons.
NOTE:
After setting date or time,
allow at least 60 seconds before
powering down the relay or the new
setting may be lost.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...