3.58
SEL-311C Relay
Instruction Manual
Date Code 20060320
Distance, Out-of-Step, Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Frequency Elements
NFREQ =
60 Hz
(nominal system frequency is 60 Hz)
E81
≥
2
(enable frequency element 2)
81D2P =
59.65 Hz
(frequency element 2 pickup)
With these settings:
81D2P < NFREQ
the underfrequency part of frequency element 2 logic is enabled. 81D2 and
81D2T operate as underfrequency elements. 81D2 is used in
testing only
.
Frequency
Element Operation
.
Overfrequency Element Operation
With the previous overfrequency element example settings, if system
frequency is
less than or equal to
61.25 Hz (81D1P = 61.25 Hz), frequency
element 1 outputs:
81D1 = logical 0 (instantaneous element)
81D1T = logical 0 (time delayed element)
If system frequency is
greater than
61.25 Hz (81D1P = 61.25 Hz), frequency
element 1 outputs:
81D1 = logical 1 (instantaneous element)
81D1T = logical 1 (time delayed element)
Relay Word bit 81D1T asserts to logical 1 only after time delay 81D1D.
Underfrequency Element Operation
With the previous underfrequency element example settings, if system
frequency is
less than or equal to
59.65 Hz (81D2P = 59.65 Hz), frequency
element 2 outputs:
81D2 = logical 1 (instantaneous element)
81D2T = logical 1 (time delayed element)
Relay Word bit 81D2T asserts to logical 1 only after time delay 81D2D.
If system frequency is
greater than
59.65 Hz (81D2P = 59.65 Hz), frequency
element 2 outputs:
81D2 = logical 0 (instantaneous element)
81D2T = logical 0 (time delayed element)
Frequency Element Voltage Control
and
Note that all six frequency elements are controlled by the same undervoltage
element (Relay Word bit 27B81). Relay Word bit 27B81 asserts to logical 1
and blocks the frequency element operation if any voltage (V
A
, V
B
, or V
C
)
goes below voltage pickup 27B81P. This control prevents erroneous frequency
element operation following fault inception.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...