Instruction Manual
Date Code 20060320
Loss-of-Potential, CCVT Transient Detection, Load-Encroachment, and Directional Element Logic
Load-Encroachment Logic
encroachment logic only operates if the positive-sequence current (I
1
) is
greater than the Positive-Sequence Threshold shown in
. For a
balanced load condition, I
1
= phase current magnitude.
Forward load (load flowing out) lies within the hatched region labeled
ZLOUT. Relay Word bit ZLOUT asserts to logical 1 when the load lies within
this hatched region.
Reverse load (load flowing in) lies within the hatched region labeled ZLIN.
Relay Word bit ZLIN asserts to logical 1 when the load lies within this
hatched region.
Relay Word bit ZLOAD is the OR combination of ZLOUT and ZLIN:
ZLOAD =
ZLOUT + ZLIN
Settings Ranges
.
Load-Encroachment
Setting Example
Example system conditions:
The PTs are connected line-to-neutral.
Convert Maximum Loads to Equivalent Secondary Impedances
Step 1. Start with maximum forward load:
a. 800 MVA • (1/3) = 267 MVA per phase
b. 230 kV • (1/
√
3) = 132.8 kV line-to-neutral
c. 267 MVA • (1/132.8 kV) • (1000 kV/MV) = 2010 A
primary
d. 2010 A primary • (1/CT ratio)
= 2010 A primary • (1 A secondary/400 A primary)
= 5.03 A secondary
e. 132.8 kV • (1000 V/kV) = 132800 V primary
Table 4.1
Load-Encroachment Logic Settings Ranges
Setting
Description and Range
ZLF
Forward Minimum Load Impedance;
corresponding to maximum load flowing out
ZLR
Reverse Minimum Load Impedance;
corresponding to maximum load flowing in
0.05–64.00
Ω
secondary (5 A nominal phase current inputs,
IA
,
IB
,
IC
)
0.25–320.00
Ω
secondary (1 A nominal phase current inputs,
IA
,
IB
,
IC
)
PLAF
Maximum Positive Load Angle Forward (–90° to +90°)
NLAF
Maximum Negative Load Angle Forward (–90° to +90°)
PLAR
Maximum Positive Load Angle Reverse (+90° to +270°)
NLAR
Maximum Negative Load Angle Reverse (+90° to +270°)
Nominal Line-Line Voltage:
230 kV
Maximum Forward Load:
800 MVA
Maximum Reverse Load:
500 MVA
Power Factor (Forward Load): 0.90 lag to 0.95 lead
Power Factor (Reverse Load): 0.80 lag to 0.95 lead
CT ratio:
2000/5 = 400
PT ratio:
134000/67 = 2000
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...