K.6
SEL-311C Relay
Instruction Manual
Date Code 20060320
Unsolicited Fast SER Protocol
Functions and Function Codes
If the relay determines that SER records have been lost, it sends a message
with the following format:
XX
Response number (XX = 00, 01, 02, 03, 01, 02...)
00000000
Four bytes reserved for future use as a return routing address.
dddd
Two-byte day of year (1–366)
yyyy
Two-byte, four-digit year (e.g., 1999 or 07CF hex)
mmmmmmmm
Four-byte time of day in milliseconds since midnight
XX
1st element index (match with the response to the
SNS
command; 00 for 1st element, 01 for second element, and so on)
uuuuuu
Three-byte time tag offset of 1st element
in microseconds since time indicated in the time of day field.
XX
2nd element index
uuuuuu
Three-byte time tag offset of 2nd element in
microseconds since time indicated in the time of day field.
•
•
•
xx
last element index
uuuuuu
Three-byte time tag offset of last element in
microseconds since time indicated in the time of day field.
FFFFFFFE
Four-byte end-of-records flag
ssssssss
Packed four-byte element status for
up to 32 elements (LSB for the 1st element)
cccc
Two-byte CRC-16 checkcode for message
Table K.4
Format of Message if SER Records Have Been Lost
(Sheet 1 of 2)
Data
Description
A546
Message header
22
Message length (34 decimal)
0000000000
Five bytes reserved for future use as a routing address.
YY
Status Byte
01 = need acknowledgement
03 = settings changed and need acknowledgement
18
Function code
C0
Sequence byte (Always C0. Other values
are reserved for future use in multiple frame messages.)
XX
Response number (XX = 00, 01, 02, 03, 00, 01, ...)
00000000
Four bytes reserved for future use as a return routing address.
dddd
Two-byte day of year (1–366) of overflow message generation
yyyy
Two-byte, four-digit year (e.g., 1999 or 07CF hex)
of overflow message generation.
mmmmmmmm
Four-byte time of day in milliseconds since midnight
FFFFFFFE
Four-byte end-of-records flag
Table K.3
Message Format for Function Code 18
(Sheet 2 of 2)
Data
Description
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...