14.14
SEL-311C Relay
Instruction Manual
Date Code 20060320
Application Settings for SEL-221 Series Relays
SEL-221G-5 to SEL-311C Settings Conversion Guide
Convert SEL-221G-5
Output Mask Logic
Settings to SEL
OGIC
Control Equations
See
Programmable Output Contact Mask Settings
in
Section 5: Applications
in the SEL
-221G-5 Instruction Manual
for a description of output masks. In
the SEL-311C, output masks are replaced by SEL
OGIC
control equations as
ORDER Q
V
I
= 32QE
= 32VE
= 32IE
Directional Control for Ground
Distance and Residual Ground
Overcurrent Elements on
page 4.9
Section 2—Directional Elements
79OI1
= 79OI1
Section 6: Close and Reclose
Logic
Section 5—Reclose Logic
79OI2
= 79OI2
79OI3
= 79OI3
79RSD
None (SEL-221G setting 79RS serves a
slightly different purpose.)
Reclosing Relay Timer Settings
on page 6.14
Section 6—79RS Timer Eliminates
Standing Close
79RSLD
None
52AEND
= 52BT (Pickup
Switch-Onto-Fault Trip Logic
on page 5.7
Section 5—High Set Phase Over-
current Setting (50H)
SOTFD
= 52BT (Dropout)
Z3XPU
None (221G-5 fixed at 2 cycles)
Directional Comparison Block-
ing Logic on page 5.25
Section 5—Zone 2 Short Phase
Time Delay; Zone 2 Short Residual
Overcurrent Time Delay
Z3XD
None (221G-5 fixed at 5 cycles
BTXD
None (221G-5 fixed at 0.5 cycles)
21SD
= Z2SP
67SD
= Z2SG
TDURD
= TDUR
Section 5—Trip Duration Timer
(TDUR)
SV1PU
= 50MFD
a
SEL-311C phase-to-phase fault detector settings 50PP1, 50PP2, and 50PP3 are set to 0.1 •I
NOM
and are hidden. This corresponds to
SEL-221G-5 setting 50L.
b
Curve U1 in the SEL-311C is slightly different from curve 1 in the SEL-221G-5. Time dial adjustments may be necessary.
c
The SEL-221G-5 uses a circular out-of-step characteristic. The SEL-311C uses a quadrilateral out-of-step characteristic.
Table 14.5
SEL-311C Settings Calculated From SEL-221G-5 Settings
(Sheet 3 of 3)
SEL-311C
Setting
a
Calculated From SEL-221G-5 Settings
SEL-311C Instruction
Manual Section
SEL-221G-5 Instruction
Manual Section
Table 14.6
SEL-311C SEL
OGIC
Control Equation Equivalent to Each
SEL-221G-5 Mask Logic Setting
SEL-221G-5 Settings Mask
SEL-311C SEL
OGIC
Control Equations
MTU
TR
MPT
SV2 (DTT)
MTB
TRCOMM
MTO
TRSOTF
MA1
OUT104
MA2
OUT105
MA3
OUT106
MA4
OUT107
MRI
79RI
MRC
79DTL
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...