Instruction Manual
SEL-311C Relay
Testing and Troubleshooting
Test Procedures
Equation 13.2
Coincidentally, these voltage and current signals could represent a forward
single line-ground fault on a system with a 90° impedance angle. Normally, a
forward fault results in a negative Z2c value.
Here is an example for a reverse single line-ground fault.
∠
Z1ANG = 90°
V
2
= 10
∠
180° volts, secondary
I
2
= 2
∠
90° amps, secondary
Equation 13.3
is positive for a reverse fault and
negative for a forward fault. This result is consistent with actual behavior on
the power system.
The relay determines fault direction by comparing the result of
to forward and reverse impedance thresholds that are dependent upon the Z2F
and Z2R relay settings and the magnitude of negative-sequence voltage
divided by the magnitude of negative-sequence current.
When Z2c is less than the forward Z2 threshold, Z2FT, the fault is in the
forward direction, so the relay sets the F32Q and F32QG elements, if other
supervisory conditions permit. When Z2c is greater than the reverse Z2
threshold, Z2RT, the fault is in the reverse direction, so the relay sets the R32Q
and R32QG elements, if other supervisory conditions permit.
The forward directional threshold is calculated through use of
when Z2F is negative or
when Z2F is positive.
When Z2F
≤
0:
Equation 13.4
When Z2F
>
0:
Equation 13.5
Where:
Equation 13.6
The reverse directional threshold is calculated through use of
when Z2R is negative.
Z2c
Re 10 180
°
1 90
°
∠
2
90
°
–
∠
•
(
)
•
∠
*
[
]
2
2
--------------------------------------------------------------------------------------------
=
–20 ohms
4
-----------------------
=
–5 ohms
=
Z2c
Re 10 180
°
1 90
°
∠
2 + 90
°
∠
•
(
)
•
∠
*
[
]
2
2
----------------------------------------------------------------------------------------------
=
20 ohms
4
--------------------
=
5 ohms
=
Z2FT
0.75
Z2F
0.25
Z2m
•
–
•
=
Z2FT
1.25
Z2F
0.25
Z2m
•
–
•
=
Z2m
V
2
I
2
---------
=
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...