13.13
Date Code 20060320
Instruction Manual
SEL-311C Relay
Testing and Troubleshooting
Relay Testing
k. Press
{SELECT}
.
l.
Use the left, right, up and down arrow keys to change
the setting to:
LL = 99.00
m. Press
{SELECT}
.
n. Press
{EXIT}
.
o. Press
{SELECT}
(YES)
to save the new settings.
Purpose:
Test the fault locator.
Method:
Step 1. Test the fault locator by using the voltages and currents in
.
These voltages and currents were obtained for various locations
and fault types, assuming a radial line with a source impedance
of 0.2 times the total 100-mile line impedance.
Step 2. Run ground fault tests by using the test source connections
. Run phase-
to-phase fault tests by using the test source connections shown
in
Faults at 75 miles are within Zone 1, since the Zone 1 reach setting is
80 percent of the 100-mile line positive-sequence impedance (see Z1P,
Z1MG, and XG1 in the settings). Faults at 85 miles are beyond Zone 1, but
within Zone 2.
Faults listed in
cause certain combinations of output contacts to
close and front-panel LEDs to illuminate. You can use the front-panel LCD
functions to examine the short form fault data following each test.
shows the expected results.
Table 13.2
Fault Locator Test Values
Location
Type
VA
VB
VC
IA
IB
IC
Units
75 miles
AG
52.89
0.00
69.97
–124.30
70.34
124.10
5.24
–82.40
0.00
0.00
0.00
0.00
V or A
Degrees
BC
67.00
0.00
56.75
–126.20
56.75
126.20
0.00
0.00
7.83
–174.00
7.83
6.00
V or A
Degrees
85 miles
AG
54.24
0.00
69.67
–123.90
70.00
123.70
4.74
–82.40
0.00
0.00
0.00
0.00
V or A
Degrees
BC
67.00
0.00
57.69
–125.50
57.69
125.50
0.00
0.00
7.08
–174.00
7.08
6.00
V or A
Degrees
Table 13.3
Output Contact and Target LED Results
Location
Type
Output Relays
Target LEDs
75 miles
AG
OUT1, OUT2, OUT4
INST, Zone 1, A, G
75 miles
BC
OUT1, OUT2, OUT4
INST, Zone 1, B, C
85 miles
AG
OUT1, OUT2, OUT4
TIME, Zone 2, A, G
85 miles
BC
OUT1, OUT2, OUT4
TIME, Zone 2, B, C
NOTE:
To simplify this step, apply dc
voltage to the
IN101
input. The relay
recognizes the asserted input when
applied dc voltage is approximately
equal to the Logic Input voltage rating
shown on the relay identification
sticker. Input
IN101
is programmed to
monitor the breaker auxiliary contact,
52A. Energize the
IN101
input for the
duration of this step to block the
Switch-Onto-Fault logic from
operating. If dc voltage source is not
available, set ESOTF = N in the relay
settings.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...