2.24
SEL-311C Relay
Instruction Manual
Date Code 20060320
Installation
Circuit Board Connections
If an output contact is operating as an “extra alarm” (driven by the same signal
that operates the dedicated
ALARM
output contact), it will be in the
opposite
state
of the dedicated
ALARM
output contact in a
standard relay shipment
. In
a standard relay shipment, the dedicated
ALARM
output contact comes as a b
type output contact and all the other output contacts (including the “extra
alarm”) come as a type output contacts.
The output contact type for any output contact can be changed (see
). Thus, the dedicated
ALARM
output contact and
the “extra alarm” output contact can be configured as the same output contact
type if desired (e.g., both can be configured as b type output contacts).
Password and
Breaker Jumpers
Table 2.3
Move Jumper JMP 23 to Select Extra Alarm
Position
Output Contact OUT107 Operation
Output contact
OUT107
is operated by Relay
Word bit OUT107. Jumper JMP23 comes
in this position in a
standard relay ship-
ment
“Extra Alarm” output contact is operated
by alarm logic/circuitry. Relay Word bit
OUT107 does not have any effect on output
contact
OUT107
when jumper JMP23 is in
this position (see
(1)
(2)
(3)
JMP23
(1)
(2)
(3)
JMP23
Table 2.4
Password and Breaker Jumper Operation
Jumper
Jumper Position
Function
Password JMP6-A
ON
(in place)
Disable password protection
a
for serial ports and front panel.
a
View or set the passwords with the
PASSWORD
command (see
OFF
(removed/not in place)
Enable password protection
for serial
ports and front panel. Passwords are
enabled in a
standard relay shipment
.
Breaker JMP6-B
ON
(in place)
Enable serial port commands
OPEN
,
CLOSE
, and
PULSE
b
.
These commands are disabled
in a
standard relay shipment
.
b
The
OPEN
,
CLOSE
, and
PULSE
commands are used primarily to assert output contacts for circuit
breaker control or testing purposes (see
Section 10: Serial Port Communications and
OFF
(removed/not in place)
Disable serial port commands
OPEN
,
CLOSE
, and
PULSE
. These commands
are disabled in a
standard relay ship-
ment
.
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...