Date Code 20060320
Instruction Manual
SEL-311C Relay
Installation
Circuit Board Connections
Output Contact
Jumpers
shows the correspondence between output contact jumpers and the
output contacts they control. The referenced figures show the exact location
and correspondence. With a jumper in the A position, the corresponding
output contact is an a type output contact. An a type output contact is closed
when the associated SEL
OGIC®
control equation is asserted, and open when
the associated SEL
OGIC
equation is deasserted. With a jumper in the B
position, the corresponding output contact is a b type output contact. A b type
output contact is closed when the associated SEL
OGIC
equation is deasserted,
and open when the associated SEL
OGIC
equation is asserted. These jumpers
are soldered in place.
, note that the
ALARM
output contact is a b type output contact
and the other output contacts are all a type output contacts. This is how these
jumpers are configured in a
standard relay shipment
. Refer to
and
for examples of output contact operation for different output
contact types.
“Extra Alarm” Output
Contact Control
Jumper
All the SEL-311C relays have dedicated alarm output contacts (labeled
ALARM
—see
, and
). Often more than one
alarm output contact is needed for such applications as local or remote
annunciation, backup schemes, etc.
Convert the output contact adjacent to the dedicated
ALARM
output contact to
operate as an “extra alarm” output contact by moving jumper JMP23 on the
main board (see
With the jumper in one position, the output contact operates regularly. With
the jumper in the other position, the output contact is driven by the same
signal that operates the dedicated
ALARM
output contact (see
Table 2.2
Output Contact Jumpers and Corresponding Output Contacts
SEL-311C
Model Number
Output
Contact Jumpers
Corresponding
Output Contacts
Reference
Figures
0311C00
x
and 0311C01
x
JMP21–JMP29
(but not JMP23)
ALARM
–
OUT101
0311C01
x
JMP17–JMP28
OUT212
–
OUT201
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...