7.7
Date Code 20060320
Instruction Manual
SEL-311C Relay
Inputs, Outputs, Timers, and Other Control Logic
Local Control Switches
Local Control Switches
The local control switch feature of this relay replaces traditional
panel-mounted control switches. Operate the sixteen (16) local control
switches using the front-panel keyboard/display (see
Interface (Only on Models With LCD)
The switch representation in this figure is derived from the standard:
Graphics Symbols for Electrical and Electronics Diagrams IEEE Std 315-1975,
CSA Z99-1975, ANSI Y32.2-1975, 4.11 Combination Locking and Nonlocking Switch,
Item 4.11.1.
Figure 7.4
Local Control Switches Drive Local Bits LB1 Through LB16
The output of the local control switch in
is a Relay Word bit LB
n
(
n
= 1–16), called a local bit. The local control switch logic in
repeats for each local bit LB1–LB16. Use these local bits in SEL
OGIC
control
equations. For a given local control switch, the local control switch positions
are enabled by making corresponding label settings.
Note the first setting in
n
) is the overall switch name setting.
Make each label setting through the serial port using the command
SET T
.
View these settings using the serial port command
SHO T
(see
Section 10: Serial Port Communications and
Local Control
Switch Types
Configure any local control switch as one of the following three switch types:
ON/OFF Switch
Local bit LB
n
is in either the ON (LB
n
= logical 1) or OFF (LB
n
= logical 0)
position.
Table 7.1
Correspondence Between
Local Control Switch Positions and Label Settings
Switch Position
Label
Setting
Setting Definition
Logic State
not applicable
NLB
n
Name of
Local Control Switch
not applicable
ON
SLB
n
“Set” Local bit LB
n
logical 1
OFF
CLB
n
“Clear” Local bit LB
n
logical 0
MOMENTARY
PLB
n
“Pulse” Local bit LB
n
logical 1 for one
processing interval
Logical 1
LBn
(n = 1 through 16)
ON Position
(Maintained Logical 1
Position)
OFF Position
(Maintained Logical 0 Position)
MOMENTARY Position
(Logical 1 for One Processing Interval)
Relay
Word
Bit
NOTE:
On SEL-311C relays without an
LCD, the Relay Word bits LB1–LB16 are
always = logical 0. (Local bit control is
not possible because there are no
front-panel buttons or displays on the
relay.)
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...