Setting the Relay
Settings Explanations
Settings Explanations
Note that most of the settings in the settings sheets that follow include
references for additional information. The following explanations are for
settings that do not have reference information anywhere else in the
instruction manual.
Identifier Labels
Relay Settings (Serial Port Command SET and Front Panel) on
The SEL-311C has two identifier labels:
➤
the Relay Identifier (RID)
➤
the Terminal Identifier (TID)
The Relay Identifier is typically used to identify the relay or the type of
protection scheme. Typical terminal identifiers include an abbreviation of the
substation name and line terminal.
The relay tags each report (event report, meter report, etc.) with the Relay
Identifier and Terminal Identifier. This allows you to distinguish the report as
one generated for a specific breaker and substation.
RID and TID settings may include the following characters: 0–9, A–Z, #, &,
@, -, /, ., space. These two settings cannot be made via the front-panel
interface.
Current Transformer
Ratios
Relay Settings (Serial Port Command SET and Front Panel)
Phase and polarizing current transformer ratios are set independently.
Line Settings
Relay Settings (Serial Port Command SET and Front Panel)
Line impedance settings Z1MAG, Z1ANG, Z0MAG, and Z0ANG are used in
distance relaying, fault locator (see
) and in
automatically making directional element settings Z2F, Z2R, Z0F, and Z0R
(see
Settings Made Automatically on page 4.21
). A corresponding line length
setting (LL) is also used in the fault locator.
The line impedance settings Z1MAG, Z1ANG, Z0MAG, and Z0ANG are set
in
Ω
secondary. To convert line impedance (
Ω
primary) to
Ω
secondary:
Ω
primary • (CTR/PTR) =
Ω
secondary
where:
CTR = phase (
IA
,
IB
,
IC
) current transformer ratio
PTR = phase (
VA
,
VB
,
VC
) potential transformer ratio (wye-connected)
Line length setting LL is unitless and corresponds to the line impedance
settings. For example, if a particular line length is 15 miles, enter the line
impedance values (
Ω
secondary) and then enter the corresponding line length:
LL =
15.00 (miles)
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...