7.36
SEL-311C Relay
Instruction Manual
Date Code 20060320
Inputs, Outputs, Timers, and Other Control Logic
Rotating Default Display (Only on Models With LCD)
Rotating Default Display (Only on Models With LCD)
The rotating default display on the relay front panel replaces indicating panel
lights. Traditional indicating panel lights are turned on and off by circuit
breaker auxiliary contacts, front-panel switches, SCADA contacts, etc. They
indicate such conditions as:
➤
circuit breaker open/closed
➤
reclosing relay enabled/disabled
Traditional
Indicating Panel
Lights
shows traditional indicating panel lights wired in parallel with
SEL-311C optoisolated inputs. Input
IN101
provides circuit breaker status to
the relay, and input
IN102
enables/disables reclosing in the relay via the
following SEL
OGIC
control equation settings:
52A =
IN101
79DTL =
!IN102
[= NOT(IN102); drive-to-lockout setting]
Figure 7.29
Traditional Panel Light Installations
corresponds to
.
Reclosing Relay Status Indication
79 ENABLED
panel light illuminates when the “79 Enable”
switch is closed. When the “79 Enable” switch is open, the
79 ENABLED
panel
light extinguishes, and it is understood that the reclosing relay is disabled.
Circuit Breaker Status Indication
BREAKER CLOSED
panel light illuminates when the 52a
circuit breaker auxiliary contact is closed. When the 52a circuit breaker
auxiliary contact is open, the
BREAKER CLOSED
panel light extinguishes, and it
is understood that the breaker is open.
Traditional
Indicating Panel
Lights Replaced
With Rotating
Default Display
The indicating panel lights are not needed if the rotating default display
feature in the SEL-311C is used.
shows the elimination of the
indicating panel lights through use of the rotating default display.
79
Enable
BREAKER
CLOSED
79
ENABLED
52a
SEL-311C
(+)
IN102
(—)
IN101
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...