7.37
Date Code 20060320
Instruction Manual
SEL-311C Relay
Inputs, Outputs, Timers, and Other Control Logic
Rotating Default Display (Only on Models With LCD)
Figure 7.30
Rotating Default Display
Replaces Traditional Panel Light Installations
There are sixteen (16) of these default displays available in the SEL-311C.
Each default display has two complementary screens (e.g.,
BREAKER CLOSED
and
BREAKER OPEN
) available.
General Operation of
Rotating Default
Display Settings
The display settings are enabled using the EDP setting. Set EDP to the number
of display settings that are desired (N, 1–16).
SEL
OGIC
control equation display point setting DP
n
(
n
= 1–16) controls the
display of corresponding, complementary text settings:
DP
n
_1 (displayed when DP
n
= logical 1)
DP
n
_0 (displayed when DP
n
= logical 0)
Make each text setting through the serial port, using the command
SET T
.
View these text settings by using the serial port command
SHO T
(see
Section 10: Serial Port Communications and
). These text settings are displayed on the SEL-311C front-panel
display on a time-variable rotation through use of Global setting SCROLD
(see
Rotating Default Display on page 11.12
for more specific operation
information).
The following settings examples use optoisolated inputs
IN101
and
IN102
in the
display points settings. Local bits (LB1–LB4), latch bits (LT1–LT4), remote
bits (RB1–RB8), setting group indicators (SG1–SG6), and any other
combination of Relay Word bits in a SEL
OGIC
control equation setting can
also be used in display point setting DP
n
.
Settings Examples
The settings examples provide the replacement solution shown in
for the traditional indicating panel lights in
Reclosing Relay Status Indication
Make SEL
OGIC
control equation display point setting DP1:
DP1 =
IN102
Make corresponding, complementary text settings:
DP1_1 =
79 ENABLED
DP1_0 =
79 DISABLED
Display point setting DP1 controls the display of the text settings.
79
Enable
52a
SEL-311C
(+)
IN102
(—)
IN101
79 ENABLED
BREAKER CLOSED
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...