Backfeed Voltage Level
If the
Test on Backfeed
setting is set to the
Block
option on the
Operation
screen, enter the
percentage of system phase-to-phase voltage on the load side above which a
PulseClosing
Technology
or
Close-Testing
operation is prevented. (Range: 5-100; Step: 1%;
Default: 10)
Note:
This check will not be performed if the IntelliRupter fault interrupter is in a
Pole-
Mismatch
state as the result of a single-phase trip.
Power Factor Sign Convention
This setting determines the sign convention applied to both the power factor DNP analog
input points and the power factor values displayed on the
Metering
screen. (Range: IEC
or IEEE; Default: IEC) See Figure 12.
Figure 12. The sign convention diagram.
For
IEC
mode, the power factor sign is solely dependent on the direction of Real Power
flow and is independent of the load being inductive or capacitive.
• The power factor is positive for normal (positive) Real Power flow; that is, when Real
Power flows into the load.
• The power factor is negative for reverse (negative) Real Power flow; that is, when Real
Power flows out of the load.
For
IEEE
mode, the power factor sign is solely dependent on the nature of the load
being capacitive or inductive.
• For an inductive load, the power factor is negative.
• For a capacitive load, the power factor is positive.
S&C Instruction Sheet 766-530 25
General Setup