Local Battery Indication
The LED flash pattern for Local Battery Indication (½ second on, ½ second off) can be
turned on or off. This should be set to the
Off
setting when no battery is installed because
a Low Battery or Bad Battery indication is unnecessary.
Remote Off Indication
The LED flash pattern (solid on) indicating the
Remote Operation
mode is set to the
Off
mode can be turned on or off, and the default is the
Off
setting.
Blink Pattern Priority
Only one blink pattern can be displayed at a time. The highest priority condition (indicated
by lower number) will always be displayed:
1. Error (or Battery Low/Bad if enabled) = Flashes ½ second every second
2. Remote Off = Solid On (A Manual Lever command causes a temporary 10-second solid
On.)
3. Wi-Fi connected = Pulses Dim to Bright
4. Loop Restoration is timing or Ready or IntelliTeam is Ready = Flashes 3 times
(½ second On—½ second Off) every 30 seconds
5. Normal operation = On ½ second every 30 seconds
6. IntelliRupter fault interrupter not powered or inoperative = Off
Open Source Operation Screen Control
When this setpoint is set to the
Show Control
mode, the
Open-Source Sectionalizing
(Enabled/Blocked) button is shown at the lower-right side of the
Operation
screen.
Block Manual Lever If Maintenance Mode
(R2 control only)
When the
Block Manual Lever If Maintenance Mode
setpoint is set to the
Yes
state
and the
External Interface Maintenance Mode
input is active, the OPEN and CLOSE
manual control levers and the
Operation
screen
Open
and
Close
commands will be
prevented from opening or closing the IntelliRupter fault interrupter.
Block External Trip Inputs When Maintenance Mode
(R2 control only)
When the
Block External Trip Inputs When Maintenance Mode
setpoint is set to
the
Yes
state and the
External Interface Maintenance Mode
command is active, the
External Interface Trip
,
Open
, and
Close
commands will be prevented from opening
or closing the IntelliRupter fault interrupter.
S&C Instruction Sheet 766-530 29
General Setup