Figure 88. The
Setup>Communications>DNP
screen.
Local Device DNP Address
Enter the network address for this control. It must be the same as the DNP/RTU address
on the
Setup>Restoration>IntelliTeam SG>Team Summary
screen. Be sure to enter
an address even if this control will not be accessed via SCADA or a remote IntelliLink
software connection. (Must be greater than 0; Default: 1; Maximum: 65519)
NOTICE
Changing the DNP address or other communication parameter can prevent
the control from communicating with other team members in an IntelliTeam SG
system and via SCADA or a remote IntelliLink software connection . If
communication is lost with a control, you must go to the site, connect through
IntelliLink software and reset the communication parameter that had been changed .
DNP communication settings for the IntelliTeam SG Automatic Restoration System,
SCADA, and IntelliLink Setup Software are configured on the
DNP
screen. See Figure 88.
DNP Configuration
144 S&C Instruction Sheet 766-530
Communication Setup