Review the “Computer Requirements” and “Software Installation” sections in
Instruction Sheet 766 -571, “IntelliRupter® PulseCloser® Fault Interrupter:
Software Installation
.”
NOTICE
Install and use only the IntelliLink Setup Software supplied for IntelliRupter fault
interrupter . IntelliLink Setup Software furnished with other S&C products cannot be
used to access an IntelliRupter fault interrupter .
NOTICE
A remote or local upgrade puts a control into the
Prohibit Restoration state . When
upgrading controls in an IntelliTeam SG system, use the following procedure:
STEP 1.
Upgrade the control software . This can be done with IntelliLink Setup
Software .
STEP 2.
After the upgrade, verify all settings were preserved .
STEP 3.
Use IntelliTeam Designer Version 6 .0 .x .x to re-push IntelliTeam SG system
configurations to all FeederNets that have updated devices .
STEP 4.
If a device is an open point, push the configuration to both FeederNets for
that device .
STEP 5.
Verify the team configurations .
STEP 6.
For IntelliNode™ Interface Modules only, set the
External Device Data
Updated mode to the Running setting .
STEP 7.
Enable the
Automatic Restoration mode on all upgraded controls .
Coordinaide software can plot various TCC curves for a protection overcurrent element
direction. The curves appropriate for both the upstream and downstream protective
devices can then be selected, and their parameters downloaded to a Setpoints Group File
for uploading to the IntelliRupter fault interrupter control. A Setpoints Group File can
also be downloaded from a control and opened using Coordinaide software for evaluation.
T he l i nk to Coord i na ide sof t wa re is located on t he S&C website at:
sandc.com/en/support/coordinaide/
. When selected, the link the opening page has a
brief description of the protection applications Coordinaide software can handle. When
launching the program, the next page contains the Conditions of Use disclaimer, the
minimum Web browser requirements, and a link to the Coordinaide software users guide.
After agreeing to the Conditions of Use, one final click launches the program.
Requirements and
Installation
Coordinaide™—
The S&C Protection
& Coordination
Assistant
S&C Instruction Sheet 766-530 9
IntelliRupter
®
Fault Interrupter Software