Reset—
Select the inverse curve reset method from the drop-down list:
D/T
(Definite
Time) or
E/M
(Electromechanical) mode.
Reset Time—
When the
Definite Time
reset mode is selected, enter the reset delay time
(in seconds). (Range: 0.000-600.000; Step: 0.001)
Definite Time 1 Min. Trip—
This is the current (in primary amperes) at which the
Definite Time 1
element picks up. (Range: 6-16,000; Step: 1) The stated maximum is
for 15-kV IntelliRupter fault interrupters; 27-kV and 38-kV are limited to 12,500 amps
maximum.
Definite Time 1 Min. Time—
This is the time delay (in seconds) after which the
Definite
Time 1
element trips. (Range: 0.000-600.000; Step: 0.001)
Definite Time 2 Min. Trip—
This is the current (in primary amperes) at which the
Definite Time 2
element picks up. (Range: 6-16,000; Step: 1) The stated maximum is
for 15-kV IntelliRupter fault interrupters; 27-kV and 38-kV are limited to 12,500 amps
maximum.
Definite Time 2 Min. Time—
This is the time delay (in seconds) after which the
Definite
Time 2
element trips. (Range: 0.000-600.000; Step: 0.001)
Ground Overcurrent
The
Ground Overcurrent
element trips the IntelliRupter fault interrupter when the
computed residual of the three-phase elements exceeds the pickup value for the time
value set by the inverse curve or the definite time delay.
Ground Check box—
Check to enable this element.
Inverse Segment—
Select from the drop-down list of inverse curve names or select
the
None
option. Only the
Definite Time
settings will be used when the
None
option
is selected.
Min. Trip—
This is the current (in primary amperes) at which the inverse curve begins
timing. (Range: 6-16,000; Step: 1) The stated maximum is for 15-kV IntelliRupter fault
interrupters; 27-kV and 38-kV are limited to 12,500 amps maximum.
Min. Time—
This is the time (in seconds) that defines the fastest response of the inverse
curve portion of the TCC curve. (Range: 0.000-100.000; Step: 0.001)
Time Mult—
This is the time modifier for the inverse curve. (Range: 0.01-15.00; Step: 0.01)
Time Adder—
This is the time modifier for the inverse curve. (Range: -10.000-100.000;
Step: 0.001)
Low Cutoff—
This is the current (in primary amperes) at which the TCC curve begins
timing. This value must be equal to or greater than the lowest pickup value of the inverse
curve, the
Definite Time 1
element, and the
Definite Time 2
element. (Range: 6-16,000;
Step: 1) The stated maximum is for 15-kV IntelliRupter fault interrupters; 27-kV and
38-kV are limited to 12,500 amps maximum.
Reset—
Select the reset method for the inverse curve from the drop-down list. Select
the
D/T
(Definite Time) or
E/M
(Electromechanical) mode.
Reset Time—
When the
Definite Time
reset mode is selected, enter the reset delay time
(in seconds). (Range: 0.000-600.000; Step: 0.001)
S&C Instruction Sheet 766-530 101
Protection Setup