Figure 63. The
Setup>Restoration>Loop
screen.
Profile Name
The profile names were configured on the
Setup>Protection>General Profile x>Direction
1 Current>Initial Trip
screen (on the
Initial Trip
screen for each of the four profiles).
They are shown on the
Setup>Restoration>Loop
screen for reference.
Enable Loop Restoration
This setting enables or disables the
Loop Restoration
mode for each general profile.
Direction
For each general profile, select the direction or directions for which the
Loop Restoration
mode is allowed to pick up load. This parameter is not available if the
Loop Restoration
mode is disabled. For example, if Direction 1 is specified, the
Loop Restoration
mode
will only attempt to pick up loads served in Direction 1. Select the
Direction 1
or
Direction 2
option to configure a one-way tie. Select the
Both Directions
option to
allow the
Loop Restoration
mode to pick up load on either side. This setting applies to
both the
Normally Closed
and
Normally Open
states.
Direction 1 and Direction 2
The direction names were configured on the
Setup>General>Site Related>System
screen
and are shown here for reference. See Figure 63.
Profile Configuration
Options
116 S&C Instruction Sheet 766-530
Loop Restoration