Figure 57. The
Setup>Protection>Closing Profile 1>Closing Profile 1 – Current>Closing
Profile Main
screen.
The
Closing Profile 2
option can be used instead of the
Closing Profile 1
option on
a one-time basis by setting it as the selected closing profile on the
Operation
screen. It
can also be applied by operating the IntelliRupter fault interrupter OPEN/CLOSE/READY
lever twice within the configured
Time for External Lever Closing Delay
Timer
.
The
Closing Profile 2
option is typically implemented when difficulties such as false
trips are encountered during closing using the
Closing Profile 1
option. The
Closing
Profile 2
option is setup in the same manner as the
Closing Profile 1
option, with one
major difference. To ensure successful closing, S&C recommends the
PulseClosing
Technology
and
Sync Check
modes not be enabled in the
Closing Profile 2
option.
These parameters should remain configured in the default
No
setting.
The closing profiles are time-limited by the configuration of the
Time for Closing
Profile to be Active
Timer
. The
Synch Check
function may be performed before
executing a
Closing Profile
operation when both sides of the IntelliRupter fault
interrupter are energized.
Profile Name
Specify the name for the
Closing Profile 1
option, up to 12 characters in length. It is
edited in the “Closing Profile Main” section of the
Closing Profile 1
option (this tab and
section) and is displayed on each screen and sub-screen for the profile. See Figure 57.
Closing Profile
98 S&C Instruction Sheet 766-530
Protection Setup