Figure 111. The
Setup>Security
screen.
Only a user logged in as Admin user can make changes to this screen. The User Group
name can be changed for all groups except the Admin and Viewer groups. All passwords
can be changed. See Figure 111.
A dialog box will open when the value to be changed is clicked on. Changes will not
take effect until the
Apply
command is selected on the
Setup>Validate/Apply
screen.
IntelliLink Remote Commands
When set to the
Enabled
setting, IntelliLink Remote Setup Software can be used to
access the device operation commands. The
Disabled
setting is the default.
For all device types, these commands are not available when this is set to the
Disabled
setting:
IntelliTeam SG Restoration—
On the
IntelliTeam SG>Team Summary
screen
Clear Manual Operation—
On the
IntelliTeam SG>Team Summary
screen
For IntelliRupter fault interrupters, these commands are not available when this set-
ting is set to
Disabled
mode:
Switch Open—
On the
Operation
screen
Switch Close—
On the
Operation
screen
Hot Line Tag—
On the
Operation
screen
Single Phase Trip—
On the
Operation
screen
Ground Trip—
On the
Operation
screen
Test on Backfeed—
On the
Operation
screen
Circuit Testing—
On the
Operation
screen
Sensitive Earth Trip—
On the
Operation
screen
Clear Latched Overcurrent—
On the
Operation
screen
Change—
Active General Profile on the
Operation
screen
Change—
Active Closing Profile on the
Operation
screen
Remote Operation—
On the
Operation
screen
Request Open—
On the
Diagnostics>Tests
screen
Request Close—
On the
Diagnostics>Tests
screen
Request Pulse Close—
On the
Diagnostics>Tests
screen
Pulse Test—
On the
Diagnostics>Tests
screen
Battery Test—
On the
Diagnostics>Tests
screen
Security Screen
174 S&C Instruction Sheet 766-530
Security