On Next Power-up, Use Settings From:
Select from the drop-down list. Select the
Control Once
or
Control Always
options
when the IntelliRupter fault interrupter was previously configured and those control
settings will be used. When the protection-and-control module is a replacement, select
the
Base Memory
option. The replacement module will be configured with the settings
stored in the base memory module. Settings are stored for:
Block Ground Trip
,
Use 2nd
Closing Profile
,
HLT Set by SCADA
,
HLT Set by Wi-Fi
,
HLT Set by IntelliLink
,
Block Circuit Testing
,
Block Test on Backfeed
,
Block SEF Trip
,
Block Single
Phase Trip
,
Remote Operation
, and the active
General
functions.
On Next Power-up, Use Command States From:
Select from the drop-down list. Select the
Control Once or Control Always
options
when the IntelliRupter fault interrupter was previously configured and those command
states will be used. When the protection-and-control module is a replacement, select
the
Base Memory
option. The replacement module will be configured by the command
states stored in the base memory module. States are stored for these functions:
•
Ground/Neg-Seq Trip Enable/Block
•
Loop Restoration Enable/Disable
•
Circuit Testing Enable/Block
•
Test on Backfeed Enable/Block
•
Sensitive Earth Trip Enable/Block
•
Single-Phase Trip Enable/Block
•
Remote Operation Enable/Disable
•
HLT Set by SCADA, HLT Set by IntelliLink.
•
Latched Overcurrent Execute
When the GROUND TRIP manual lever is in the
Blocked
state, it takes precedence
over the saved user command state.
When the HOT LINE TAG manual lever is in the
On
state, it takes precedence over
the saved user command state.
On Next Power-up, Use Netlist From:
Select from the drop-down list. Select the
Control Once
or
Control Always
options
when the IntelliRupter fault interrupter was previously configured and that Netlist will
be used. When the protection-and-control module is a replacement, select the
Base
Memory
option. The replacement module will be configured with the Netlist stored in
the base memory module.
Timed Shut Down after Loss of AC Voltage
Select the
Yes
option to require timer expiration before shutdown. The
No
option is the
default.
Time to Disconnect Battery After Loss of Ac Voltage
This setting configures the timer. (Range: 1-240; Step: 1 minute; Default: 120)
S&C Instruction Sheet 766-530 17
General Setup