background image

GLOBAL  RX NC

Operation and maintenance instructions for air handling units 

without controls.

GLOBAL PX/RX

GLOBAL PX

GLOBAL PX

FW

Summary of Contents for Swegon Global PX

Page 1: ...GLOBAL RX NC Operation and maintenance instructions for air handling units without controls GLOBAL PX RX GLOBAL PX GLOBAL PXFW ...

Page 2: ...s of Machinery Directive 2006 42 EC Complies also with applicable requirements of the following EC directives 2014 30 EU EMC 2009 125 EC Ecodesign Regulation nr 1253 2014 LOT 6 2014 35 EU Low voltage directive 2011 65 EU RoHS 1907 2006 EC REACH Authorized to compile the technical file Name Nicolas Pary Adress Parc industriel de Sauvenière 102 Chaussée de Tirlemont B5030 Gembloux Signature Place an...

Page 3: ...ING FAN GLOBAL PXFW Counterflow 800 1200 2000 3000 4000 6000 Yes electrical Yes electrical or water Left Right Forward FW GLOBAL PX Counterflow 800 1200 2000 3000 4000 6000 Yes electrical Yes electrical or water Left Right Backward GLOBAL RX Rotary 05 08 10 12 13 14 16 20 24 26 No Yes electrical or water Left Right Backward ...

Page 4: ... place make sure that all joints are covered with insulation and are well taped Duct connections duct ends should be covered during storage and installation in order to avoid condensation inside of the unit Check that there are no foreign objects in unit ducting system or functional sections The unit is packed to prevent damage of the external and internal parts of the unit dust and moisture penet...

Page 5: ...ualified Electrician Warning Hazardous voltage OUTDOOR AIR Air from outdoor to the AHU SUPPLY AIR Air from the AHU to the building EXTRACT AIR Air from the building to the AHU EXHAUST AIR Air from the AHU to outdoor COOLING COIL BA NV KW HEATING COIL WATER ELECTRICAL SILENCER GD CT MOTORIZED DAMPER SLIP CLAMP SC MS FLEXIBLE CONNECTION CIRCULAR DUCT CONNECTION ER For inlet SR For outlet ...

Page 6: ...however possible to change the direction afterwards but only by an accredited Service technician Main version described in the manuals is always the hand right version Product Overview RIGHT HAND UNIT SUPPLY AIR TO THE RIGHT LEFT HAND UNIT SUPPLY AIR TO THE LEFT GLOBAL RX GLOBAL RX GLOBAL PX GLOBAL PX GLOBAL PX FW GLOBAL PX FW ...

Page 7: ... control signal The power supply is 24VDC 6A The fans are to be connected to a mains power supply the fan speed RPM will have to be controlled with a 0 10VDC control signal The 0 10VDC control signal can be connected to the supplied fan control cable The electrical connection box is not included For units equiped with a rotary heat exchanger a rotation monitor is factory fitted The sensor is norma...

Page 8: ...door air side 6 Pre heating electrical antifrost coil accessory 7 Drain pan and drain pipe 8 Modulating 100 by pass standard 9 M5 ePM10 50 filter on extract air side 10 Damper at exhaust air side accessory 11 Flexible connection accessory 12 Slip Clamps accessory GLOBAL PX FW NC COMPONENTS This document is an overview of technical specifications Please do refer to our selection software for detail...

Page 9: ... h 580 l s 1105 1635 1230 320 200 m h 56 l s 1360 375 100 m h 28 l s 3150 m h 875 l s 1475 1635 1230 370 300 m h 83 l s 1360 415 100 m h 28 l s 4200 m h 1165 l s 1845 1635 1230 505 400 m h 111 l s 1360 545 200 m h 56 l s 5250 m h 1455 l s 2135 1635 1600 655 500 m h 139 l s 1760 685 200 m h 56 l s 6300 m h 1750 l s 2135 1635 1600 685 600 m h 167 l s 1760 710 This document is an overview of technica...

Page 10: ...Heating coil connections 13 Internal post heating water or electrical coil accessory 14 Damper at outdoor air side accessory 15 Damper at exhaust air side accessory 17 Flexible connection accessory 18 Slip Clamps accessory 19 Water connection for postheating accessory GLOBAL RX NC COMPONENTS This document is an overview of technical specifications Please do refer to our selection software for deta...

Page 11: ...ALU 400 m h 115 l s 2400 m h 670 l s 995 1680 1465 360 14 300 m h 83 l s 3200 m h 890 l s 1182 1680 1465 375 14 ALU 400 m h 110 l s 3150 m h 875 l s 1182 1680 1465 380 16 300 m h 83 l s 3350 m h 930 l s 1182 1680 1465 380 16 ALU 400 m h 110 l s 3400 m h 945 l s 1182 1680 1465 385 18 600 m h 167 l s 4500 m h 1250 l s 1382 1880 1725 520 18 ALU 500 m h 140 l s 4000 m h 1110 l s 1382 1880 1725 500 20 ...

Page 12: ... s 1260 m h 350 l s 68 68 2000 FW 100 m h 28 l s 2100 m h 580 l s N A N A 2000 200 m h 56 l s 115 115 3000 FW 100 m h 28 l s 3150 m h 875 l s N A N A 3000 300 m h 83 l s 122 122 4000 FW 100 m h 28 l s 4200 m h 1165 l s N A N A 4000 400 m h 111 l s 137 137 5000 FW 200 m h 56 l s 5250 m h 1455 l s N A N A 5000 500 m h 139 l s 187 187 6000 FW 200 m h 56 l s 6300 m h 1750 l s N A N A 6000 600 m h 167 ...

Page 13: ... 300 m h 83 l s 2600 m h 720 l s 88 88 13 ALU 400 m h 110 l s 2400 m h 670 l s 115 116 14 300 m h 83 l s 3200 m h 890 l s 93 93 14 ALU 400 m h 110 l s 3150 m h 875 l s 120 116 16 300 m h 83 l s 3350 m h 930 l s 89 92 16 ALU 400 m h 110 l s 3400 m h 945 l s 120 116 18 600 m h 167 l s 4500 m h 1250 l s 200 200 18 ALU 500 m h 140 l s 4000 m h 1110 l s 141 141 20 600 m h 167 l s 5150 m h 1430 l s 200 ...

Page 14: ...ECTIONS APPENDIX 1 PLC FANS 1 2 CONTROL CABLE 0 10V V cc ac 12 24VDC or 16 18VAC 0 10V Motor start at signal 0 8V Motor stop at signal 0 7V 1V minum torque 10V maximum torque RPM feedback rotation speed 60pulses sec 100rpm ...

Page 15: ...30 V D10A 10kA AC3 GLOBAL RX 08 ALU 3 1 A 6 2 A 1 x 230 V D10A 10kA AC3 GLOBAL RX 10 ALU 5 7 A 11 4 A 1 x 230 V D16A 10kA AC3 GLOBAL RX 10 ALU 5 7 A 11 4 A 1 x 230 V D16A 10kA AC3 GLOBAL RX 12 ALU 5 6 A 11 2 A 1 x 230 V D16A 10kA AC3 GLOBAL RX 12 ALU 5 6 A 11 2 A 1 x 230 V D16A 10kA AC3 GLOBAL RX 13 ALU 5 3 A 10 5A 1 x 230 V D16A 10kA AC3 GLOBAL RX 13 ALU 5 3 A 10 5A 1 x 230 V D16A 10kA AC3 GLOBAL...

Page 16: ... 10kA AC3 GLOBAL RX 10 2 5 A 5 0 A 1 x 230 V D6A 10kA AC3 GLOBAL RX 10 2 5 A 5 0 A 1 x 230 V D6A 10kA AC3 GLOBAL RX 12 3 7 A 7 3 A 1 x 230 V D10A 10kA AC3 GLOBAL RX 12 3 7 A 7 3 A 1 x 230 V D10A 10kA AC3 GLOBAL RX 13 3 6 A 7 2A 1 x 230 V D10A 10kA AC3 GLOBAL RX 13 3 6 A 7 2A 1 x 230 V D10A 10kA AC3 GLOBAL RX 14 3 8 A 7 5A 1 x 230 V D10A 10kA AC3 GLOBAL RX 14 3 8 A 7 5A 1 x 230 V D10A 10kA AC3 GLOB...

Page 17: ...17 2 2 ALUMINUM NON PLC FAN 1X230V Imax fan A Imax unit A SUPPLY VOLTAGE RECOMMENDED FUSES GLOBAL PX 4000 6 6 A 13 2 A 1 x 230 V D16A 10kA AC3 ...

Page 18: ...18 3 2 A 6 3 A 3 x 400 V N D10A 10kA AC3 GLOBAL RX 20 3 4 A 6 7 A 3 x 400 V N D10A 10kA AC3 GLOBAL RX 20 3 4 A 6 7 A 3 x 400 V N D10A 10kA AC3 GLOBAL RX 24 3 3 A 6 5 A 3 x 400 V N D10A 10kA AC3 GLOBAL RX 24 3 3 A 6 5 A 3 x 400 V N D10A 10kA AC3 GLOBAL RX 26 3 4 A 6 7 A 3 x 400 V N D10A 10kA AC3 GLOBAL RX 26 3 4 A 6 7 A 3 x 400 V N D10A 10kA AC3 ...

Page 19: ...19 2 4 ALUMINUM NON PLC FAN 3X400V Imax fan A Imax unit A SUPPLY VOLTAGE RECOMMENDED FUSES GLOBAL PX 5000 2 9 A 5 8 A 3 x 400 V N D16A 10kA AC3 GLOBAL PX 6000 2 9 A 5 8 A 3 x 400 V N D16A 10kA AC3 ...

Page 20: ...T 3 2 ROTARY EXCHANGER STEP DRIVER 3 3 ROTARY EXCHANGER ROTATION MONITOR Normally open contact will close at each rotor revolution Max 48 VDC 0 5A DC 10 W max Any DC combination of V A not to exceed their individual max s Contact Resistance max 150 mOhms 0 5V 50mA ...

Page 21: ...21 4 1 0 10V CONTROLLED ELECTRICAL COILS APPENDIX 4 ELECTRICAL COILS ...

Page 22: ...m refer to troubleshooting section Check the state of filter clogging Replace filters if necessary Filters that are too clogged can generate the following problems Insufficient ventilation Excessive increase of fan rotation speed Excessive sound levels Excessive power consumption power consumption will increase exponentially to an increase in pressure drop for a constant airflow Unfiltered air pas...

Page 23: ...ary to force the bypass actuator open Always clean against the direction of the airflow Cleaning must only be done by blowing with compressed air vacuum cleaning with a soft nozzle or through wet cleaning with water and or solvent Before you begin cleaning cover adjacent functional sections to protect them If cleaning solvent is used do not use solvent that will corrode aluminium or copper 4 Fan m...

Page 24: ...We make every breath count Version 14 01 2019 We reserve the right for changes ...