2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 99 / 176
12.1.2 Output setting the 2
nd
screen
▶
It sets control related parameter.
⑩
It sets the operation method of PID control.
☞
Refer to [12.1.2.1 Operation direction]
⑪
It sets the period for control output operation in case of “SSR (SOLID STATE RELAY)” control output.
⑫
It disconnects the output by PID and sends the output in emergency in case of STOP and S.OPN.
⑬
It sets the excessive integration prevention ratio (Data) which are adopted in operation of excessive
integration prevention function.
☞
Refer to [12.1.2.3 Excessive integration prevention].
⑭
It is used for overall controlling the PID data manually depending on the system characteristics after
auto tuning.
☞
Control output = PID X Control time constant (GAIN)
☞
Refer to [12.1.2.4 Control time constant]
⑮
It sets the increasing change rate of the output when the control output is increased.
16
It sets the decreasing change rate of the output when the control output is decreased.
17
The page moves up/down from the present screen.
표 12-2. Output setting the 2
nd
screen parameter
Parameter
Setting range
Unit
Initial data
DIRECTION
REV, FWD
ABS
REV
CYCLE TIME
1~300 SEC
ABS
2
PRESET OUTPUT
-5.0~105.0%
%
0.0
ARW
0.0(AUTO), 0.0 ~ 200.0%
%
100.0
AT-GAIN
0.1~10.0
ABS
1.0
UP RATE
0.0(OFF) ~ 100.0 %/SEC
%/초
0.0(OFF)
DOWN RATE
0.0(OFF) ~ 100.0 %/SEC
%/초
0.0(OFF)
①
②
③
⑤
④
[Fig. 12-5] Output setting the 2
nd
screen
⑥
⑦
⑧