2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 159 / 176
▶
When the temperature sensor is set in DCV, the following screen is displayed.
①
It sets the scope of use for the voltage input sensor.
②
It sets the display scale for the input voltage.
③
It sets the digit under the decimal point.
Table 22-1. Sensor input setting the 1
st
screen parameter of sub channel
Parameter
Setting range
Unit
Initial data
Sensor type
Refer to [Table 22-2 Sensor No.]
ABS
4
TC-K2
Decimal point
0 ~ 3
ABS
1
(When sensor group is DCV.)
Thermocouple display
T/C, TC+RJC, RJC
ABS
TC+RJC
(When sensor group is T/C.)
Upper limit range
EU
EU(100.0%)
Lower limit range
EU(0.0 ~ 100.0%)
Lower limit range < Upper limit
range
EU
EU(0.0%)
Input calibration
EUS (-100.0 ~ 100.0%)
EUS
EUS(0.0%)
Sensor filter
0 ~ 120 sec
ABS
0
SCALE upper limit
℃
100.0
(When sensor group is DCV.)
SCALE lower limit
-199.9 ~ 3000.0℃
SCALE lower limit < SCALE upper
limit
℃
0.0
(When sensor group is DCV.)
* The upper limit/lower limit for the sensor group, sensor type, upper limit.lower limit of the scope, display unit
scale upper limit/lower limit cannot be changed during operation.
[Fig. 22-6] Sensor input setting of sub channel (In case of DVC)
③
①
②