SAMWONTECH
2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 111 / 176
13.2 Other signal relay setting
13.2.1 Other signal relay setting the 1
st
screen
▶
It is a screen to set the operation signal and sensor disconnection signal.
①
It sets the operation (RUN) signal relay and delay time. .
☞
The set relay is “ON” after the set delay time.
②
It sets the sensor disconnection signal relay and keeping time.
☞
The set relay is “ON,” when the sensor is disconnected during operation.
☞
The relay stays in “ON” during the setting time, and operation state is maintained later on in case of
sensor disconnection.
③
It sets standby (WAIT) signal and holding time.
④
Setting the stationary timer signal relay, deviation, delay time and operation time
☞
Deviation : | Present value(PV) – Set value (SP)|≤the relay is “ON” during operation time (M.S)
from deviation till delay time (H.M) Namely, the relay is “ON” during operation time (M.S) when the
data of | Present value(PV) – Set value (SP)| is within the deviation.
☞
Delay time : The set relay is “ON” after the set delay time is elapsed.
☞
Operation time : The set relay is “OFF” after the set operation time elapse
when the stationary timer
signal relay operation state is maintained.
☞
Operation only in stationary operation
☞
Stop or operation time = The relay is “OFF” when 00.00 M.S is input
☞
The processing time is continued out of the deviation during relay time operation.
⑤
It moves the page up/down.
[Fig. 13-7] Other signal relay setting the 1
st
screen
①
②
③
④
⑤