SAMWONTECH
2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 163 / 176
▶
It changes every channel parameter simultaneously.
Table 22-3. Sub channel control output setting screen parameter
Parameter
Setting range
Unit
Initial data
Control output
type
SSR, SCR
ABS
SSR
Operation direction
Reverse operation, normal
operation
ABS
Reverse operation
Output period
1~300 SEC
ABS
2
Increasing change
rate
0.0(OFF) ~ 100.0 %/SEC
%/초
0.0(OFF)
Decreasing
change rate
0.0(OFF) ~ 100.0 %/SEC
%/초
0.0(OFF)
Output in case of
emergency
-5.0~105.0%
%
0.0
Excessive
integration
prevention
0.0(AUTO), 0.0 ~ 200.0%
%
100.0
Control time
constant
0.1~10.0
ABS
1.0
[Fig. 22-8] Sub channel control output