SAMWONTECH
2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 46 / 176
▶
Tuning point calculation in zone type shall be made as follows.
①
Tuning point : 1
☞
PID1 range auto tuning is performed.
Boundary data1 – Lower limit range
-
PID1 auto tuning setting data=
Lower limit
range +
2
②
Tuning point : 2
☞
PID2 range auto tuning is performed.
Boundary data2 – Boundary data1
-
PID2 auto tuning setting data=
Boundary data1 +
2
③
Tuning point : 3
☞
PID3 range auto tuning is performed.
Boundary data3 – Boundary data2
-
PID3 auto tuning setting data=
Boundary data2 +
2
④
Tuning point : 4
☞
PID4 range auto tuning is performed.
Boundary data4 – Boundary data3
-
PID4 auto tuning setting data=
Boundary data3 +
2
⑤
Tuning point : 5
☞
PID5 range auto tuning is performed.
Upper limit range – Boundary data4
-
PID5 auto tuning setting data=
Boundary data4 +
2
⑥
Tuning point : 6
☞
PID6 range auto tuning is performed.
Upper limit range – Lower limit range
PID6 auto tuning setting data=
Lower limit range
+
2
⑦
Tuning point : Auto
☞
The a1 in PID1 ~ 6 range is processed sequentially.
☞
The auto tunned PID data is saved into PID1 ~ 6 range.
Boundary data1 – Lower limit range
-
PID1 auto tuning setting data=
Lower limit range +
2
Boundary data2 – Boundary data1
-
PID2 auto tuning setting data=
Boundary data1 +
2
Boundary data3 – Boundary data2
-
PID3 auto tuning setting data=
Boundary data2 +
2
Boundary data4 – Boundary data3
-
PID4 auto tuning setting data=
Boundary data3 +
2
Upper limit range – Boundary data4
-
PID5 auto tuning setting data=
Boundary data4 +
2
Upper limit range – Lower limit range
PID6 auto tuning setting data=
Lower limit range +
2
Summary of Contents for Temp 2000 M
Page 1: ...Instruction Manual...