SAMWONTECH
2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 174 / 176
▶
It changes every channel parameter simultaneously.
Table 22-10. Sub channel PID group setting screen parameter
Parameter
Setting range
Unit
Initial data
CH#n.proportional
range
0.0(ON/OFF control) 0.1~1000.0%
%
5.0
CH#n.integration time
0~6000 SEC
ABS
120
CH#n.differentiation
time
0~6000 SEC
ABS
30
CH#n.output upper limit
%
100.0
CH#n.output lower limit
0.0~100.0 %
output lower limit < output upper limit
%
0.0
CH#n.calibration data
-5.0~105.0 %
%
100.0
* #n : 1 ~ 6