2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 61 / 176
5.2 Pattern repetition setting
▶
It is a screen to set the function for the entire set pattern or partial repetition.
▶
In addition, the motion can be set in pattern operation termination.
①
The pattern No. to perform the repetition operation is set.
②
It sets the repetition operation frequency of the set pattern.
③
It sets the pattern No. to be operated continuously at the termination of operation for the set pattern.
④
It sets the segment to start the partial repetitive operation out of the set patterns.
☞
When the starting segment is ‘1,’ it starts with start setting data (SSP) regardless of starting condition
(STC).
⑤
It sets the segment to terminate the partial repetitive operation out of set pattern.
⑥
It sets the repetition frequency of partial repetitive operation out of the set patterns.
⑦
It displays the experiment name of the set pattern.
☞
The change of experiment name is available only in [5.6 Experiment name setting].
☞
The change is impossible as it is only for reading. .
⑧
It sets to decide the next motion when the set pattern operation is terminated.
☞
Operation stop: The pattern termination signal is created and the program stops.
☞
SEG hold: It is operated with the last operation s1 and the holding state is maintained.
☞
Connection operation: The pattern which is set the connection pattern is operated.
Table5-2. Repetition setting parameter
Parameter
Setting range
Unit
Initial data
Pattern No.
1~80
ABS
1
Repetition frequency
0 (Infinite repetition)~999
ABS
1
Connection pattern
1~80
ABS
1
Motion in pattern termination
Operation stop, SEG hold,
Continuous operation
ABS
Operation stop
Segment for starting of the
repetition setting 1~4
0~99
ABS
0
Termination segment of
repetition setting 1~4
0~99
ABS
0
Repetition frequency 1~4
setting
0~99
ABS
0
①
②
④
⑧
⑦
⑤
⑥
③
[Fig. 5-3] Screen for repetition setting of pattern and segment