2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 123 / 176
▶
Explanation of HIGH, LOW deviation operation
☞
HIGH deviation operation Operation
①
Middle SP < Present indication value(PV) ≤ Upper limit SP
Present indication value(PV) ≥ Present set value(SP) + HIGH deviation : Operation will be ‘ON’.
Present indication value(PV) < Present set value(SP) + HIGH deviation : Operation will be ‘OFF’.
☞
LOW deviation Operation
②
Upper limit SP ≤ Present indication value(PV) < Middle SP
Present indication value(PV) ≥ Present set value(SP) – LOW deviation : Operation will be ‘ON’.
Present indication value(PV) < Present set value(SP) – LOW deviation : Operation will be ‘OFF’.
※
Refer to the [16.2 ON/OFF signal operation].