15. Inner signal (IS)
15.1 Inner signal setting
▶
This is the screen where objects of application, types and contents about operation for respective inner
signal can be set.
▶
8 types of inner signal operations(IS1∼IS8) can be set.
▶
Inner signal operation range and delay time can be set in the [Fig. 15-1 Inner signal setting the 1
st
screen].
①
Set Inner Signal Application Type.
☞
SP : Present Setting Point
☞
PV : Process Value
-
When selected to PV, it has hysteresis of EUS 0.5%(Not Changeable).
☞
TSP : Target Setting Point for Program Control.
②
Set Inner Signal Operation Band.
☞
Within Range : Inner Signal becomes ON when current value of Inner Signal Type is within the
High/Low Operation Range.
☞
Out of Range : Inner Signal becomes ON when current value of Inner Signal Type is out of the
High/Low Operation Range.
①
②
③
④
[Fig. 15-1] Inner signal setting the 1
st
screen
Within Range
Operation
IS Range Low
Sensor Range Low
Sensor Range High
IS Range High
Inner Signal ON Section
Out of Range
Operation
Out of Range
Operation
IS Range Low
Sensor Range Low
Sensor Range High
IS Range High
Inner Signal ON Section
Inner Signal ON Section