2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 176 / 176
ENGINEERING UNITS
– EU, EUS
EU, EUS units are used to explain CONTROLLER PARAMETER.
▶
Parameters with unit displayed with EU(), EUS() are changed proportional to existing Data when there is
change in Sensor Type (IN-T) or Hight/Low Limit in Input Range (INRH, INRL). (Hight & Low Range Limit
set value is initialized in this case.)
▪
EU( ) : Engineering Unit Value according to Range of Instrument
▪
EUS( ) : Engineering Unit Range according to the Span of Instrument
▶
Range of EU(), EUS()
Range
Center Line
EU(0 ~ 100%)
RL ~ RH
| RH – RL | / 2 + RL
EU(-100 ~ 100%)
- ( | RH – RL | + | RL | ) ~ RH
RL
EUS(0 ~ 100%)
0 ~ | RH – RL |
| RH – RL | / 2
EUS(-100 ~ 100%)
- | RH – RL | ~ | RH – RL |
0
(Example)
▶
INPUT = T/C(K2)
▶
RANGE = -200.00℃(RL) ~ 1370.00℃(RH)
Range
Center Line
EU(0 ~ 100%)
- 200.00 ~ 1370.00℃
585.00℃
EU(-100 ~ 100%)
- 1770.00 ~ 1370.00℃
- 200.00℃
EUS(0 ~ 100%)
0 ~ 1570.00℃
785.00℃
EUS(-100 ~ 100%)
- 1570.00 ~ 1570.00℃
0.00℃
EU(0 ~ 100%)
EU(-100 ~ 100%)
| RH – RL |
EUS(0 ~ 100%)
| RH – RL |
RL 0 RH
EUS(-100 ~ 100%)
| RL |
| RH |
RL : Input Range Low Limit
RH : Input Range High Limit