Installation
- 2.20 -
PCS 200 Kit
2.9.5 Safety switch
The connection to a safety switch offers two main functions:
-
Safety function: if the contact is open, the MD cannot rotate.
-
Addressing function: during the MD addressing stage, the safety contact closes
and confirms the device address (see paragraph 3.4.2 on section 3).
The safety switch must be implemented using:
-
An electromechanical switch with
“
positive opening
”
NC contact (this condition
is shown by the symbol
)
or
-
a high-reliability electromagnetic sensor (e.g. SICK RE11-SA03 or equivalent)
☞
In order to grant the required safety level (Performance Level = c – see paragraph
1.4.7), you should foresee a safety switch having the following characteristics:
•
B10d >= 2 x 10e
6
(see note below)
☞
The safety switch is not supplied with the kit as it must be chosen according to the
dimensions requirements of the machine it will be installed on.
Note: B10d is the reliability parameter declared by the device manufacturer,
corresponding to the number of switchings which can be granted without errors.
Summary of Contents for PCS 200
Page 1: ...PCS 200 Installation Operation Maintenance ORIGINAL INSTRUCTIONS ...
Page 4: ......
Page 33: ...Installation PCS 200 Kit 2 13 Figure 2 Wiring diagram of the system without alternator ...
Page 35: ...Installation PCS 200 Kit 2 15 Figure 2 14 ECU wiring diagram ...
Page 41: ...Installation PCS 200 Kit 2 21 This page is intentionally left blank ...
Page 102: ...User Manual PCS 200 Kit 3 61 This page is intentionally left blank ...
Page 105: ...Maintenance and Troubleshooting PCS 200 Kit 4 3 4 4 SPARE PARTS ...
Page 111: ...Maintenance and Troubleshooting PCS 200 Kit 4 9 This page is intentionally left blank ...