uREG User Manual
97
Table 16.2.1. Communication settings (UART communication)
Setting designation and description
Denomination
IDENT in menu
Setting value
RS232 activity signal
used to signal interface activity by the LED (on the panel)
110 Active
signal
RS232
active, inactive
RS-232 baud speed:
transmission speed via RS232 links
111 Baud speed
for RS-232
300, 600, 1200,
2400, 4800, 9600,
19200, 23300, 28800,
38400, 57600, 115200
Parity bit RS-232:
used to set the mode of code-oriented transmission control
112 Parity bit
RS232
none, even parity,
odd parity
Duplex RS-232:
used to set bidirectional simultaneity of transmission
113 Duplex
RS232
half,
full
Logic number RS-232:
two-digit individual address of the device to make it explicitly
distinguishable among devices connected to the common
computer bus. The number is attached to messages sent to/from
the master computer to specify the message recipient.
114 Logic
number RS-232:
0
–
99
default 1
RS-232 protocol:
type of interface transmission protocol
115 Protocol
RS232
uCZIPstd
uCZIPnet
RS485 activity signal
used to signal interface activity by the LED (when ON and on the
panel)
116 Active
signal
RS485
active, inactive
Baud speed RS485/FO1:
transmission speed via interface links
117 Baud speed
for RS-485
300, 600, 1200,
2400, 4800, 9600,
19200, 28800, 38400,
57600, 76800, 115200,
138240.1728, 230400,
256000.460800, 512000,
CAN 25 kbs, CAN 125 kbps
Parity bit RS485/FO1:
used to set the mode of code-oriented transmission control
118 Parity bit
RS485
even parity,
odd parity, none
Stop bits RS485/FO1:
119 Stop bits
RS485
1 bit, 2 bits
Duplex RS485/FO1:
used to set bidirectional simultaneity of transmission
11A Duplex
RS485
half,
full,
FOring.non-light,
FOring.light,
FO.radius.non-light,
FOradius.light
Logic number RS485/FO1 (younger):
individual (16-bit MSB|LSB) address of the device to make it
distinguishable among devices connected to the common
computer bus. The number is attached to messages sent to/from
the master computer to specify the message recipient.
11B Logic number
(LSB) RS-485
0
–
255
default 1
Logic number RS485/FO1 (older):
11C Logic number
(MSB) RS-485
0
–
255
default 0
Protocol RS485/FO1:
type of interface transmission protocol
11D Protocol
RS485
uCZIPstd, uCZIPnet,DNP3,
IEC 60870-5-101,
IEC 60870-5-103,
CZIPstd, CAN-PPM2, uCZIPstd
MASTER, MCZIPStd, Modbus RTU
Slave, Modbus ASCII Slave,
Master Modbus RTU
BTS interlock for RS485/FO1:
used to activate interlock of telecontrol via RS485/FO1
11E BTS interlock
for RS485
inactive BTS,
active BTS,
Port DISABLED
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...