uREG User Manual
84
14.3.
SYSTEM REPORTS
The
u
REG
system has a special group of reports –
System reports
– whose code (index) is =
0, identified by a DEC or HEX marker. These reports cannot be redefined by the user (at the
stage of
Log
CZIP
application development) and are used to indicate malfunctions of the units
and its improper settings.
The key to event codes in system reports is presented in Table 14.3.
Table 14.3.
Attribute
DEC
Attribute
HEX
Meaning
0
0
Undefined system report
1
1
Uaux → Auxiliary power-up and start of initial calibration procedure
2
2
Uaux → Power off
…
…
Reserved
24
18
Failed settings → Error in main settings
25
19
Failed settings → Error in standby settings
26
1 A
Failed settings → Error in auxiliary settings (Transm LCD)
…
…
Reserved
32
20
Implementation of I2C bus (indication of I2C bus on LCD screen, slot in Reports)
33
21
Fixing settings: Main
34
22
Fixing settings: Backup
35
23
Change bank of settings: Main → Standby
36
24
Change bank of settings: Standby → Main
37
25
Fixing settings: Auxiliary (Transm LCD)
38
26
Fix corrections
…
…
Reserved
48
30
Error of relays
…
…
Reserved
56
38
Exceeded 1st threshold for maximum temperature inside the enclosure
…
…
Reserved
64
40
Fault of LEDs
…
…
Reserved
72
48
Fault of LCD screen
…
…
Reserved
80
50
Fault of relays → Improper current of relays
…
…
Reserved
88
58
Failed reports → Faulty readout of reports
…
…
Reserved
96
60
5V back to normal
97
61
5V → Supply below 4.70 V
98
62
5V → First instance of exceeded supply v5 V
beyond allowable range 4.75 – 5.25 V
99
63
5V → Supply below 4.55 V
100
64
1.8V → Supply of IF module below +1.75 V
101
65
1.8V → Supply of IF module below +1.85 V
102
66
5 V → Panel supply below +4.75 V
103
67
5V → Panel supply e5.25 V
104
68
12V → Panel supply below +10 V
105
69
12V → Panel supply e14 V
106
6 A
Panel temperature below normal
107
6B
Panel temperature exceeded
Display backlight will be turned off.
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...