uREG User Manual
86
15.
DATA RECORDERS
15.1.
DAR - Digital and Analog Recorder
All
u
REG
units are equipped with an additional current / voltage / digital data recorder
located in the IF-x module (also referred to as the
disturbance recorder
), which is associated
with selected events affecting protective decisions.
The recorder memory is divided into buffers.
Each buffer always records 10 electrical values:
→ Configuration with VT-0
→ Configuration with VT-2/VT-1
→ Configuration with
VT-3/VT-4
1 set of voltages and currents
2 sets of voltages, 1 set of cI0
2 sets of voltages, 2 sets of currents
Voltage U1;
• Voltage U1_1;
• Voltage U1_1;
Current I1;
• Current I1;
• Current I1_1;
Voltage U2;
• Voltage U2_1;
• Voltage U2_1;
Current I2;
• Current I2;
• Current I2_1;
Voltage U3;
• Voltage U3_1;
• Voltage U3_1;
Current I3;
• Current I3;
• Current I3_1;
Voltage U0;
• Voltage U0_1;
• Current I3_2;
Current I0;
• Current I0;
• Current I1_2;
AUXI0 input (VT);
• Voltage U1_2;
• Voltage U1_2;
Current Ig;
• Voltage U0_2;
• Current I2_2;
and
96 digital states
(outputs of functors → see
Log
CZIP
APPLICATION
).
Data are recorded in buffers in numerals (the so-called samples) with at a
standard
frequency of 1600 Hz – 32 samples per period
for each data set, according to the monitored
values directly at device terminals.
Available for each version of the
IF-x
module, the recorder memory can be configured to
support up to 10, 11 to 19 or even several tens buffers of different capacity.
In a standard solution, the following
configurations
of recorder buffers are available at 1600
Hz –
[IF-0 4MB] / [IF-4 8/16MB]
:
2*20.48 s (2 buffers, 20.48 s each),
4*10.24 s,
8*5.12 s,
16*2.56 s,
32*1.28 s,
2*40.96 s,
4*20.48 s,
8*10.24 s,
16*5.12 s,
32*2.56 s.
Additionally, the range of buffer configuration in the
IF-4
[8/16 MB]
module is
extended over
the following settings
:
2*81.92 s,
4*40.96 s,
8*20.48 s,
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...