uREG User Manual
78
13.2.
PRIMARY MEASUREMENTS
Table 13.2. Primary measurements
Description
Explanation and range
Notes
40 Current IL1
41 Current IL2
42 Current IL3
Phase current RMS value.
Range:
0 – (lower value out of: 192*thetaIf,
10000) [A]
43 Current Ifmax
The maximum value of phase current RMS
values in L1, L2, L3 – recorded after the last
circuit-breaker activation by TZ, ZW or KZ
pulse.
Range:
see primary currents. IL1-IL3
44 Current I0
I0 zero current RMS value,
Range:
0-(lower value out of: 10*theta I0,
1000)[A]
45 Current Ig
Current (Ig) RMS (e.g. in BKR lateral branch)
Range:
0-(lower value out of: 10*theta I0,
1000)[A]
46 Voltage U0
Voltage RMS of
zero sequence U0.
Range:
0 – 130* Un/(√3*100) [kV]
47 Voltage UL1
48 Voltage UL2
49 Voltage UL3
Phase voltage RMS value.
Range:
0 – 130*Un/100 [kV]
4A Voltage U12
4B Voltage U23
4C Voltage U31
Line-to-line voltage RMS value,
Range:
0 – 130*Un/100 [kV]
4D Active power P3
Three-phase active power RMS (average over
1 second) – positive value with energy to the
line, negative for the opposite direction.
Range:
0 – 100 [MW]
Power computed as a sum of marked
busbar active power values.
L1, L2 and L3
4E Reactive power Q3
Three-phase reactive power RMS value
(average over 15 second) – positive value for
inductive load, negative value for capacitive
load.
Range:
0 – 100 [Mvar]
Power computed as a sum of marked
busbar reactive power values.
L1, L2 and L3
4F Frequency
Frequency
45 – 55
[Hz]
4G Derivative df/dt
Derivative df/dt
0.1 – 25
[Hz/s]
4H P3max0 15min
4J P3max1 15min
4L P3max2 15min
4N P3max3 15min
Three-phase active peak-RMS power (moving
average over 15 minutes), in 0th, 1st, 2nd
and 3rd time zone, respectively.
Range:
0 – 100 [MW]
The determined power is an average (over
15-minute intervals – resolution --min.)
peak active or reactive power value in the
time zone after auxiliary power-on to the
unit, or after remote register reset.
Power indication is coupled with a time
marker of the maximum record.
4I Q3max0 15min
4K Q3max1 15min
4M Q3max2 15min
4O Q3max3 15min
Three-phase reactive peak-RMS power
(moving average over 15 minutes), in 0th,
1st, 2nd and 3rd time zone, respectively.
Range:
0 – 100 [Mvar]
4P Ecz+ Zone 0
4Q Ecz+ Zone 1
4R Ecz+ Zone 2
Stored active energy fed to busbars in time zones.
Range:
0 – 10 000 [MWh]
Energy metered for a period of the time
zone (successive days) for energy fed to
busbars (Ecz+)
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...