uREG User Manual
15
Dependent overcurrent protection
Activity and mode of the dependent criterion RI >
inactive, OW
Overcurrent-stage starting current I>
0.3...50 A
Time delay of 2-fold overcurrent tI>
0.05...24 s
Slope of the dependent characteristic curve wtI >
moderate,
standard, rapid
Short-circuit overcurrent protection
Tripping current setting range I>
0.1 ÷ 50 A
Internal operate time time for 2-fold overcurrent value
20 ÷ 50 ms (typical 35 ms)
Adjustable resetting ratio
0.910 ÷ 0.985
Differential overcurrent protection
Internal operate time for 2-fold overcurrent value
15 ÷ 40 ms (typical 22 ms)
Internal operate time with harmonic lock-out
25 ÷ 50 ms (typical 30 ms)
Inrush stabilization (harmonic restraint deviation)
+- 10%
Overvoltage protection [VT-0, VT-2, VT-3]
Line-to-line operating voltage of overvoltage protection U>
5 ÷ 130 V
Internal operate time for 2-fold value of exceeded setting
20 ÷ 50 ms (typical 35 ms)
Adjustable resetting ratio
0.910 ÷ 0.985
Undervoltage protection [VT-0, VT-2, VT-3]
Line-to-line operating voltage of undervoltage protection U<
5 ÷ 130 V
Internal operate time for 2-fold value of exceeded setting
20 ÷ 50 ms (typical 35 ms)
Adjustable resetting ratio
1.015 ÷ 1.059
Under and overfrequency protection
Minimum voltage threshold of protection start-up f< and f>
18 V
Internal operate time for 2-fold value of exceeded setting
60 ÷ 85 ms (typical 65 ms)
Adjustable resetting ratio for f> and f<
0.05 Hz
Measurement range
45 – 55 Hz
Frequency measurement deviation
+- 3 mHz max.
df/dt frequency derivative protection (ROCOF)
Minimum voltage threshold of protection start-up df/dt
18 V
Internal operate time for 2-fold value exceeded threshold
60 ÷ 85 ms (typical 65 ms)
Adjustable resetting ratio for f<
0.910 ÷ 0.985
Measurement range
0.1 – 25 Hz/s
Protection against contact lost with power grid (
Vector Shift
)
Recognized vector shift of line-to-line voltage vectors (in 3-phase)
within the range 0 to 60° with an accuracy of 0.5°; adjustable within 1 - 25°
Internal operate time
app. 30 ms
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...