uREG User Manual
17
Signaling relay output circuits
Rated voltage
220 V DC
Continuous current-carrying capacity
1 A
Inductive circuit breaking:
220 V DC, L/R= 40 ms
0.1 A
or
Rated voltage
250 V AC
Continuous current-carrying capacity
5 A
Breaking capacity:
220 V AC, cos
=0.4
2 A
High-break contacts relay for use with the circuit-breaker coils
OW and ZW outputs:
Rated voltage
220 V DC
Continuous current-carrying capacity
2 A
Inductive circuit breaking:
220 V DC, L/R= 40 ms
1.2 A / 300 cycles
or
Rated voltage
250 V AC
Breaking capacity
8 A
Absolute accuracy of time delays
Delays acc. to precise setting
±1.5 ms
Delays acc. to accurate setting
±20 ms
Delays acc. to rough setting
±1 s
Delays acc. to long-time setting
±1 s
Input signals absolute positioning accuracy
For DC logic input signals
<16 ms
For AC logic input signals
25 ÷ 40 ms
Explanation: This value results from filtration or input signal computation.
Power supply (PS-0)
Rated supply voltage
220 VDC (or 230 VAC)
Admissible range of supply voltage changes DC
88 ÷ 365 V DC
Admissible range of supply voltage changes AC
100 ÷ 260 V AC
Power input at 220 V DC
<15 W (typ. 7.5W)
Device readiness after power-up
3.5 s
Power supply (PS-1)
Rated supply voltage
24 VDC
Admissible range of supply voltage changes DC
21 ÷ 38 V DC
Power input at 24 V DC
<15 W (typ. 7.5W)
Device readiness after power-up
3.5 s
Insulation electric strength
For input circuits:
- sinusoidal voltage
2 kV/60 s/0.5 kVA
- surge impulse voltage
5 kV/ 1.2/50
s/0.5 J
Contacts of relays
- sinusoidal voltage
1 kV/60 s/0.5 kVA
I/O power unit
- sinusoidal voltage
2.5 kV/60 s/0.5 kVA
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...