uREG User Manual
33
7.6.
VT-0 / VT-5 MODULE (SLOT 2)
The
VT-0
module houses 4 measuring voltage transformers for U0, U1, U2, U3 and 2 current
transformers for I0 and Ig. The module additionally has 3 unipolar digital inputs (AUXI 0..2),
which can be also used for analogue measurements (sensitivity threshold selectable by setting).
Terminals of the
VT-0
module are grouped into 3 x Phoenix-Contact/Wieland slots:
8-pin MSTBA2.5/8-G strip (pitch: 5.00 mm, max 12 A, 250 V)
for measurement of
U0, U1, U2, U3
voltages within the range (Un: 100 V)
= 0 ÷ 130 V;
5-pin MSTBA2.5/5-G strip (pitch: 5.00 mm, max 12 A, 250 V)
for
AUXI0, AUXI1, AUXI2
inputs
= 0 ÷ 130 V;
4-pin GMSTBA2.5/4-G strip (pitch: 7.50 mm, max 12 A, 400 V)
for measurement of currents
I0, Ig
within the range (In: 1 A)
= 0 ÷ 10 A.
Fig. 7.6. Terminals of the VT-0 module.
The
VT-0
module (combined with
CT-0
) is required for fulfillment of the following protective
criteria and functions, e.g.:
Overvoltage U>
Tripped overvoltage U>T
Overvoltage U0>
Undervoltage U<
• Undervoltage U< (polygonal characteristic curve)
Tripped undervoltage U<T
• Single-phase undervoltage U<
Frequency
• Power directional
Frequency derivative df/dt>
• Vector Shift
Second harmonic f100Hz>
• capacitor bank /BKR/ control
AWSCz automatic unit controller
• Resistor controller
U1>, U2>, U3> for MSK
Internal fSPZ/SCO
Overcurrent earth-fault criterion I0>
• Directional overcurrent earth-fault I0k>
Overcurrent Ig>
Susceptance B0kier.>
Conductance G0>
• Conductance G0>kier.
Admittance Y0>
Admittance YY0>
Overpower for 3-phase reactive power (1 min.) Q3f> • Underpower for 3-phase reactive power (1 min.) Q3f<
Overpower for 3-phase active power (1 min.) P3f> • Underpower for 3-phase active power (1 min.) P3f<
The
VT-5
module is identical in terms of functionality, but it features increased measurement
threshold for voltages
U0, U1, U2, U3
within the range
5 – 260 V (optionally 500 V AC)
.
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...