Line-to-earth short-circuit fault protection
Starting current of Io>
50 ÷ 5000 mA
Internal start-up time for 2-fold value of exceeded setting
20 ÷ 50 ms (typical 35 ms)
Adjustable resetting ratio
0.910 ÷ 0.985
Admittance non directional protective functions
Y0>, G0>
Admittance directional protective functions
G0k>, B0k>
Current I0 vs. voltage U0 phase angle correction: fii
-90
÷ +90
Starting admittance Y0>
0.50 ÷ 50 mS
Internal start-up time for 2-fold value of exceeded setting
50 ÷ 75 ms (typical 60 ms)
Adjustable resetting ratio
0.910 ÷ 0.985
Starting conductance G0>, G0k>
0.50 ÷ 5.0 mS
Internal start-up time for 2-fold value of exceeded setting
50 ÷ 75 ms (typical 60 ms)
Adjustable resetting ratio
0.910 ÷ 0.985
Starting susceptance B0k>
0.50 ÷ 5.0 mS
Internal start-up time for 2-fold value of exceeded setting
50 ÷ 75 ms (typical 60 ms)
Adjustable resetting ratio
0.910 ÷ 0.985
Busbar protection interlock
Starting current of busbar protection interlock IZS>>
0.1 ÷ 50 A or 0.9 ÷ 100 A
Internal start-up time for 2-fold value of exceeded setting
20 ÷ 50 ms (typical 35 ms)
Adjustable resetting ratio
0.910 ÷ 0.985
Binary input circuits (IO-0 module):
Remote control (telemechanics) circuits
- rated input voltage (adjustable by settings)
24 V or 220 V DC
- input voltage range (24V)
17 ÷ 32 V
or (220 V)
88 ÷ 253V
- current input at 24 V or 220 V
<3 mA
Other circuits:
- input voltage
88 ÷ 253 V
- current input at 220 V
< 3 mA
Special ordering option: AC inputs
230 VAC
Remote control (telemechanics) circuits (CM and CR modules):
- rated input voltage (adjustable by settings)
>20 V or >50 V
- input voltage range (24V)
20 ÷ 36 V
or (220 V)
50 ÷ 253 V
- current input at 24 V or 220 V
<3 mA
Other circuits:
- input voltage
88 ÷ 253 V
- current input at 220 V
< 3 mA
Special ordering option: AC inputs
230 VAC
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...