uREG User Manual
12
Conventional remote control (telemechanics)
by wired circuits for receiving/transmitting
signals (via terminal inputs/outputs) as an alternative to communication channels.
Operation of substations switchgear
with SF6 and enclosed switchgears (support of relief
vents).
Measurements
of true RMS values for 12 analog voltage and current signals, power coefficient
tg
or cos
and derivative values: frequency, active/reactive power and selected type of
energy (including subdivision into day-time zones) and admittance, conductance and
susceptance of earth fault branch (conditionally, when U0>U0n is satisfied), based on calculated
RMS values.
Up to
4 banks for main se 1 bank for auxiliary settings
(for transmission channels set-
points purposes).
Event log recorder
which can save
1024 reports (stored in non-volatile memory)
, each day and
time-stamped with resolution up to 100us, event code as protocol index (e.g. DNP3), and user
definable description.
Data recorder (DAR)
which records recent samples in an active circular buffer; in a standard
version, buffer memory can be organized in one of the following buffer configurations: 2 *
20.48s (ie. 2 buffers, each of 20.48s) , 4 * 10.24s, 8 * 5.12s, 16 * 2.56s, 32 * 1.28s, 2 * 40.96s, 4 *
20.48s, 8 * 10.24s, 16 * 5.12s or 32 * 2.56s.
There are always
10 electrical quantities
recorded in each buffer.
→ Example: configuration with CT-0 + VT-0:
• Voltage U12
• Current I1
• Voltage U23
• Current I2
• Voltage U31
• Current I3
• Voltage U0
• Current I0
• Input AUXI0 (VT)
• Current Ig
and
96 digital values
(states of functors).
For IF-4 modules, the range of buffer configuration is extended by the following settings:
2 * 81.92 s, 4 * 40.96 s, 8 * 20.48 s, 16 * 10.24 s and 32 * 5.12 s.
In addition, the IF-4 module (combined with MB-2/3) provides a data recorder operating at 3200
Hz (64 samples per period) and even a wider buffer configuration range and up to
192 digital
states
to be recorded.
Criteria recorder
(CDAR)
– records up to 16 selectable RMS values in max. 32 buffers with
settable recording frequency.
Time synchronization acc. to IEEE 1588 PTP with a precision of 1 us
with autonomic local
synchronization (if no supervisory system is present).
Operation together with a supervisory system via:
– two independent
RS-485
links – to be selected with one of many transmission protocols:
uCZIPstd, uCZIPnet, DNP-3.0, IEC-60870-5-101, IEC-60870-5-103, CZIPstd (backward
compatibility), Modbus, CAN-PPM2, etc. It is possible to use optical fiber cables (FO);
– 10/100 Mb
Ethernet
link – to be selected with TCP / UDP protocols (with protocol tunneling:
uCZIPstd, DNP-3.0, etc.) and IEC-60870-5-104.
Operation with a local PC
via independent communication interfaces:
RS232
and
USB
(via
uCZIPstd and uCZIPnet).
Self-check
of operational correctness of important unit elements; all semiconductor
components are manufactured according to reliable static logic (also in case of memory) for
industrial applications.
Software upgrade
– all software components (both firmware and the
APPLICATION
for a given
bay) can be reprogrammed via RS-232, RS-485 and USB.
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...